Press
to go to the following screen:
By making a choice here, the timer can be set to
operate 'manually' , with a fixed fan speed, or
'automatically' , with speed compensation as the filters
become polluted. The settings for each timer event
are shown on the timer overview screen, in the third
column from the right:
0 - OFF
1 – 3000 Automatic
2 – 3500 Automatic
3 – 4000 Automatic
4 – 4500 Automatic
5 – 5000 Automatic
6 – 3000 Manual
7 – 3500 Manual
8 – 4000 Manual
9 – 4500 Manual
PLEASE NOTE!
If you choose manual, speed 5000 is not available.
9.3
CONTROL: BOOST
PLEASE NOTE!
This function can also be selected directly
from the 'HOME' screen and is further described
in chapter 10.
9.4
CONTROL: ADJUSTING THE AIR DISCHARGE PANEL
Adjusting the air discharge panel: If the DFI is equipped with
electrically adjustable louvres (option horizontal and/or
option vertical) and this is set via the Service Menu (only
accessible to Euromate), the selection button shown here will
be visible on the home screen. When you press this button,
the 'Thrust' screen appears:
On this screen you can select which units you want to set the louvres for.
When you press a number, the button turns green to indicate that the
number has been selected. The same number in group 2 will now be locked
so that this number is not also included in group 2.
14
These buttons are used to select the DFI's
to which the created timer applies. The
selected DFI's turn green.
Now, when you press the 'manual' button, the following screen opens:
On this screen you can select how the louvres should be set for each group.
If no DFI's were selected for group 2 on the previous screen, group 2 will not
be visible on the screen shown above.
It is not possible to set a fixed angle for both vertical and horizontal.
With the
button it is possible to set the back-and-forth mode
for both vertical and horizontal at once.
To set the louvres at a fixed angle, this angle must be entered
Between -45 and +45 degrees (where 0 degrees is discharge straight ahead).
When the 'apply' button is pressed, the command will be sent and the
discharge grille will adjust itself to the entered value.
If you want the louvres to move back and forth, select the 'back and forth'
button and then press 'apply' .
10
BOOST
Setting Boost: The boost function makes it possible to
increase the flow of selected units by 10% for an hour. This
function is intended to boost the capacity of the DFI in the
event of temporary additional pollution. After the hour, the
DFI will return to its original or previous speed. When you
press this button, the 'BOOST' screen appears:
Pressing
selected DFI's.
Here you can choose which units should
temporarily run faster.
sends the command to the
.