Leviton FLX Serie Manual De Instalación Y Guía Del Usuario página 9

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3-Phase PDUs only
Bank 1 LED
Bank 2 LED
Bank 3 LED
Scrolll LED
Select Button "A"
The SELECT button "A" allows you to determine which bank information (Bank 1, Bank 2,
Bank 3, or Total) is to be shown on the meter's display. Pressing the SELECT button "A" will
cycle through the available options. The LED associated with your selection will light up on
the display.
The SELECT button "B" allows you to determine the information (Amps, Volts, or Watts)
to be shown on the meter's display. Pressing the SELECT button "B" will cycle through the
available options. The LED associated with your selection will light up on the display.
TOTAL: When selected, displays the combined power information (Amps, Volts, or Watts) for
all banks.
BANK 1: When selected, displays the power information (Amps, Volts, or Watts) for bank 1.
BANK 2: When selected, displays the power information (Amps, Volts, or Watts) for bank 2.
BANK 3: When selected, displays the power information (Amps, Volts, or Watts) for bank 3.
SCROLL: Will toggle automatically between the above options every 5 seconds and display
Amps, Volts, or Watts respectively. While in scroll mode, the user must depress the Select
Button "B" to toggle through Amps, Volts and Watts.
AMPS: When selected, displays the total Amperage for all devices connected to the selected
bank (Bank 1, Bank 2, Bank 3, or Total) on the PDU.
VOLTS: When selected, displays the total Voltage for all devices connected to the selected
bank (Bank 1, Bank 2, Bank 3, or Total) on the PDU.
WATTS: When selected, displays the total Wattage for all devices connected to the selected
bank (Bank 1, Bank 2, Bank 3, or Total) on the PDU.
When there is no load connected to the selected bank (Bank 1, Bank 2, Bank 3, or
Total) on the PDU then the LED display will read the following:
AMPS: "0.0" will be displayed on the LED display.
VOLTS: "Output Voltage" will be displayed on the LED display. If a specific bank has no
voltage applied then "----" will be displayed on the LED display.
WATTS: "----" will be displayed on the LED display.
NOTE: To reboot the web server in a Monitored PDU press and hold the
SELECT "B" button for 5 seconds. This will not erase the settings you have
entered.
3-Phase Meter Display
TOTAL
Total LED
BANK 1
BANK 2
BANK 3
SCROLL
SELECT
AMPS
VOLTS
WATTS
SELECT
LED Display
© 2009 Leviton Manufacturing Co., Inc. All Rights Reserved.
Amperage LED
Voltage LED
Wattage LED
Select Button "B"
PK-93661-10-02-0C
9

Publicidad

Tabla de contenido
loading

Productos relacionados para Leviton FLX Serie

Tabla de contenido