Qs Link Wiring - Lutron Electronics Energi Savr Node Manual De Instrucciones

Ocultar thumbs Ver también para Energi Savr Node:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
English
Español
Energi Savr Node
Step 5: QS link wiring
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power via circuit breaker before wiring or servicing the
Energi Savr NodeT with EcoSystemR unit.
Buttons and LEDs on the front of the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
QS system communications uses PELV wiring. Follow all local
and national electrical codes when installing PELV wiring with
mains wiring.

QS Link Wiring

Length
Wire Gauge
Power (terminals 1 and 2):
1 pair 1,0 mm
Less than 153 m
Data (terminals 3 and 4):
1 pair 0,5 mm
and shielded*
Power (terminals 1 and 2):
1 pair 4,0 mm
153 m to 610 m
Data (terminals 3 and 4):
1 pair 0,5 mm
and shielded*
* Alternate Data-only cable: Use approved data link cable
(0,5 mm
twisted/shielded) from Belden, model #9461.
2
A QS system can have up to 100 zones and 100 devices. The
Energi Savr NodeT with EcoSystemR unit occupies 1 device
position and up to 100 zone positions.
See diagram on the right for QS link wiring.
1. Connect terminals 1, 3 and 4 to all Energi Savr NodeT with
EcoSystemR units.
2. Each Energi Savr NodeT with EcoSystemR unit has its own built
in power supply.
3. Terminate the terminal 2 connection (24 V-) so that each control
unit supplies power up to 3 PDUs. Each QS device should receive
power from only one Energi Savr NodeT with EcoSystemR unit
(see diagram on page 8).
NOTE: To connect extra wallstations, use a separate power
supply (24 V-), and only connect COM, MUX, MUX to the
wallstations connected to the Energi Savr NodeT with
EcoSystemR unit.
4. Wiring may be daisy chained or t-tapped.
Power draw calculations are not needed for wireless inputs
or inputs connected directly to the Energi Savr NodeT with
EcoSystemR units.
International Energi Savr Node
English
Français
with EcoSystemR
TM
Available from
Lutron in one cable:
GRX-CBL-346S
2
(non plenum)
GRX-PCBL-346S
, twisted
2
(plenum)
GRX-CBL-46L
2
(non plenum)
GRX-PCBL-46L
(plenum)
, twisted
2
with EcoSystemR Installation Guide
TM
Português
Italiano
|
Installation Guide
QS Link Wiring:
• 0,5 mm
to 4,0 mm
2
2
• Strip length: 8,0 mm
• Torque: 0,5 N
m
QS Link Terminal Connections
Each QS link terminal can accept only two 1,0 mm
4,0 mm
wires (i.e. GRX-CBL-46L) will not fit. Connect as shown
2
below using appropriate wire connectors.
Single
0,5 mm
to
2
4,0 mm
2
each
Deutsch
COM
24 V
MUX
MUX
Two 1,0 mm
2
each
4,0 mm
中文
wires. Two
2
each
2