Italtecnica Sirio Manual Del Usuario página 39

Ocultar thumbs Ver también para Sirio:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 101
7.0 FACTORY SETTINGS LOADING
CAUTION: This procedure loads the "factory" parameters as for a new device; This does not mean that the parameters will be "optimized"
for the specific plant in which Sirio is installed. Then, after you have loaded the factory settings, you have to adapt them to the system
requirements.
To reload the factory default parameters, hold down the ">>" button (right arrow) while turning on the device.
The following data will not be re-initialized:
- calibration of flow and pressure sensors
- the history of alarms
- the pump operation timer
- the inverter power meter
- the pump start counter
The Imax parameter (maximum current of the motor) will be set to the value
used at the end of the production line for functional testing (between 2 and 6
A, depending on the model); It is necessary to adjust it again in relation to
the pump used.
39
IT
EN
PT
RU
DE
ES
FR
RO

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sirio entry 230Sirio entry 230 xp

Tabla de contenido