Technical parameters

Number of functions:
Supply terminals:
Voltage range:
Burden (max.):
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Supply indication:
Time ranges:
Time setting:
Time deviation:
Repeat accuracy:
Temperature coeffi cient:
Output
Number of contacts:
Current rating:
Breaking capacity:
Inrush current:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):

Other information

Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
Standards:
CRM-82TO
a - On Delay (Power On) /
e - Off Delay (S Break)
A1 - A2
AC/DC 12 - 240 V (AC 50 - 60 Hz)
AC 0.7 - 3 VA / DC 0.5 - 1.7 W
2.5 W
-15 %; +10 %
green LED
0.1 s - 10 min
potentiometer
5 % - mechanical setting
0.2 % - set value stability
0.1 % / °C, at = 20 °C (0.1 % / °F, at = 68 °F)
2x changeover / SPDT (AgNi / Silver Alloy)
8 A / AC1
2000 VA / AC1, 192 W / DC
10 A / < 3 s
250 V AC / 24 V DC
red LED
7
3x10
0.7x10
5
-20 °C to +55 °C (-4 °F to 131 °F)
-30 °C to +70 °C (-22 °F to 158 °F)
4 kV (supply-output)
any
DIN rail EN 60715
IP40 from front panel / IP10 terminals
III.
2
solid wire max. 2x 2.5 or 1x 4 /
with sleeve max. 2x 1.5 or 1x 2.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
73 g (2.6 oz.)
EN 61812-1, EN 61010-1
Function
a
U
t
e
U
t
t
More accurate setting of timing for long periods of time
Example of time setting to 8 hours period:
For rough setting use time scale 1 - 10 s on the potentiomenter.
For fi ne time setting aim for 8 s on potentiometer, then recheck accuracy (using
stopwatch etc).
On rough time setting, set potentiometer to originally desired scale 1 - 10 hours, leave
a fi ne setting as it is.
Warning
Device is constructed for connection in 1-phase main alternating current voltage and
must be installed according to norms valid in the state of application. Connection
according to the details in this direction. Installation, connection, setting and servicing
should be installed by qualifi ed electrician staff only, who has learnt these instruction
and functions of the device. This device contains protection against overvoltage
peaks and disturbancies in supply. For correct function of the protection of this
device there must be suitable protections of higher degree (A, B, C) installed in front
of them. According to standards elimination of disturbancies must be ensured. Before
installation the main switch must be in position "OFF" and the device should be de-
energized. Don´t install the device to sources of excessive electro-magnetic interference.
By correct installation ensure ideal air circulation so in case of permanent operation and
higher ambient temperature the maximal operating temperature of the device is not
exceeded. For installation and setting use screw-driver cca 2 mm. The device is fully-
electronic - installation should be carried out according to this fact. Non-problematic
function depends also on the way of transportation, storing and handling. In case of any
signs of destruction, deformation, non-function or missing part, don´t install and claim
at your seller it is possible to dismount the device after its lifetime, recycle, or store in
protective dump.
2 / 2
Delay OFF (S break) the power supply is
switched off (min. time is 0.5 s)
Off Delay (S break)