WARNINGS
Read this manual prior to use the device in order to ensure a safe and proper use.
Preserve this manual as future reference.
The installation and maintanance of the device must be carried out by qualified technical staff, adequately trained by ISEO.
The instructions should be carefully followed during installation. These instructions and any maintenance instructions should be passed on by the installer to
the user.
No modifications of any kind are permitted, except for those described in these instructions.
The product must be destined only for the use for which it is expressly designed and therefore as web server controller for civil and industrial locations.
Any other use is considered improper and dangerous.
The electrical connection must be made according to the constructor's instructions and respecting the regulations in force.
For all repairs, exclusively contact a technical assistance center authorized by the constructor.
Disconnect the power supply before carrying out any technical service that involves opening or accessing the internal parts of the product.
Dispose of the product separately from household waste, in accordance with local laws and regulations.
The calculation of the cables section must be performed by qualified staff.
Max cable length of LOCKBUS channel is 100 mt (sum of all branches).
Recommended voltage for LOCKBUS channel is 24 VDC.
In case of power failure the rechargeable battery inside the Atlas ensures power for 30 minutes max.
Ensure full recharge of the Atlas internal battery by running a full recharge cycle (24 hours), minimum every 6 months.
It is advisable to provide for an appropriate sectioning, a protection switch upstream of the transformer.
Atlas earth connection is mandatory.
Add Surge Protection Devices (SPD) to the mains, upstream the Atlas Master, when connected to Atlas Slaves, Actuators and Readers placed in outside
areas of the builing (not equipotential zones), according to the Lightning Protection Risk Assessment of your building and current legislations.
For any technical assistance or repairs, contact only Iseo Serrature or an Iseo Zero1 authorised technical centre.
Iseo Zero1 reserves the right, without prior notice, to make all the necessary modifications to the product and to the instruction manual, for quality
improvements or manufacturing or marketing needs.
Risk of explosion if the battery is replaced with an incorrect type. Dispose of used battery according to your local environmental laws and rules.
Cod.5E002012
i s e o . c o m
Iseo Serrature s.p.a
Via San Girolamo 13
25055 Pisogne (BS)
ITALIA
Tel. +39 0364 8821
iseo@iseo.com
ATTENTION
NiMH battery pack
NiMH 7,2V 1500mA
7,2 V - 1500 mAh
®
ELECTRONIC SUPPORT SERVICE
iseozero1.com
https://www.iseo.com/it/en/download