Mitsubishi Electric Lossnay LGH-150RVXT-E Instrucciones De Instalación página 19

Ocultar thumbs Ver también para Lossnay LGH-150RVXT-E:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
Function settings (continued)
No.42
Indoor temperature correction
Set the correction for the indoor temperature displayed on the
PZ-61DR-E screen by function
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
42
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No.51
Automatic ventilation mode setting
Set the pattern of conditions to go into By-pass mode in automatic
ventilation operation.
When setting Data is set "3" by PZ-61DR-E, function
and
No. 54
are available.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
(Factory setting)
SW2-7
51
ON
-
-
* Pattern A is more likely to become By-pass mode than pattern B.
Note;
The ventilation mode follows the table below.
Interlocked air conditioner
Remote controller
(Mr. Slim or City Multi)
Energy recovery
ventilation mode
Either Yes or No
By-pass ventilation
mode
Cooling/Stop
Automatic
Other than above
Eng-18
No. 37
.
Setting
The correction to
check
thermistor detection
0
-7 ˚C
1
-6 ˚C
2
-5 ˚C
3
-4 ˚C
4
-3 ˚C
5
-2 ˚C
6
-1 ˚C
7
0 ˚C
(Factory setting)
8
+1 ˚C
9
+2 ˚C
10
+3 ˚C
11
+4 ˚C
12
+5 ˚C
13
+6 ˚C
14
+7 ˚C
No. 52
,
Setting
Conditions to go into
check
By-pass mode
0
DIP-SW priority
(Factory setting)
Pattern A
Indoor temperature is 16 ˚C or more
1
Outdoor temperature is 16 ˚C or more
Indoor temperature -
outdoor temperature ≥ 0 ˚C
Pattern B
Indoor temperature is 22 ˚C or more
2
Outdoor temperature is 18 ˚C or more
Indoor temperature -
outdoor temperature ≥ 2 ˚C
3
Free setting
Lossnay
Energy recovery ventilation
mode
By-pass ventilation mode
Automatic (Follows the map)
Always energy recovery
ventilation mode
Automatic ventilation mode setting 1)
No.52
Outdoor and indoor temperature gap
Set one of conditions for By-pass mode in auto ventilation operation,
temperature gap between indoor and outdoor.
This function is N/A from Lossnay unit DIP-SW.
This function is available when setting Data 3 is selected at function
No.
51.
DIP-SW
SW No.
Setting
-
-
-
-
N/A
-
-
-
-
Automatic ventilation mode setting 2)
No.53
The lowest outdoor temperature
Set one of conditions for By-pass mode in auto ventilation operation,
minimum outdoor temperature which comes in indoor directly.
This function is N/A from Lossnay unit DIP-SW.
This function is available when setting Data 3 is selected at function
No.
51.
DIP-SW
SW No.
Setting
No. 53
,
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
PZ-61DR-E
Setting
Setting
check
check
Function No. Setting Data
0
-
(Factory setting)
-
1
-
2
-
3
52
-
4
-
5
-
6
-
7
PZ-61DR-E
Setting
Setting
check
check
Function No. Setting Data
-
0
-
1
-
2
-
3
-
4
-
5
6
-
(Factory setting)
-
7
53
-
8
-
9
-
10
-
11
-
12
-
13
-
14
-
15
Indoor temperature -
outdoor temperature
0 ˚C or more
1 ˚C or more
2 ˚C or more
3 ˚C or more
4 ˚C or more
5 ˚C or more
6 ˚C or more
7 ˚C or more
Outdoor temperature
10 ˚C or more
11 ˚C or more
12 ˚C or more
13 ˚C or more
14 ˚C or more
15 ˚C or more
16 ˚C or more
17 ˚C or more
18 ˚C or more
19 ˚C or more
20 ˚C or more
21 ˚C or more
22 ˚C or more
23 ˚C or more
24 ˚C or more
25 ˚C or more

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Lossnay lgh-200rvxt-eLossnay lgh-250rvxt-e

Tabla de contenido