- If enabled (as set by the factory) the Telecom Module calls ALL Telephone Num-
bers which are programmed for Telemonitoring and are associated with an event.
- If disenabled the Telecom Module will end the call as soon as one such call succe-
eds to get through.
Ø Call all voice Messages Numbers
- If enabled (as set by the factory) Telecom Module calls ALL Telephone Numbers
which are programmed to send a Voice Message associated with an event.
- If disenabled the Telecom Module will end the call as soon as one such call succe-
eds to get through.
n Messages Page
The Messages page programs Voice Message parameters, as described below.
Ø Fixed Messages - This section shows the descriptions assigned to the first se-
ven recorded Messages.
- Message 1: Header Mess.
- Message 2: Alarm Mess.
- Message 3: Fault Mess.
- Message 4: Logic Fault Mess.
- Message 5: Pre-Alarm Mess.
- Message 6: Warning Mess.
- Message 7: Walk Test Mess.
These descriptions could NOT be changed.
Ø General Messages - In this section it would be possible to assign a description of
up to 20 letters at the most to the Message nos. from 8 to 32.
n Events Page
The Events page allows the programming, for each event which is recognized by
the Control panel, of the Telephone Numbers to be dialled, the Event Code and the
Voice Message to be sent, as described below.
Events
The Events column shows the events which are recognized by the Control panel.
Alarm Numbers/Fault Numbers/General Numbers The Alarm Numbers/Fault
Numbers/General Numbers refer to the Telephone Numbers in the memory of the
Listings Page. Select the Telephone Numbers which have to be called for each
event: a symbol will indicate that the corresponding Telephone number shall be cal-
led by the corresponding event.
+
The Telephone Numbers from no. 1 to no. 8 could only be called by Alarm and
Pre-AlarmEvents. The Telephone Numbers from no. 9 to no. 16 could only be
called by Fault, Warning and Test Events. The Telephone Numbers from no. 17
to no. 32 could be called by all events.
C-ID The C-ID column shows the Event Code which is sent by the corresponding
event, when a Telephone Number which is programmed for Telemonitoring is called
with ID Contact Protocol (see the Listings Page) : digitize the Event Code which
identifies the corresponding event, in ID Contact format (three hexadecimal digits).
The factory Event Codes appear in Table 2 at page 10.
SIA The SIA column shows the Event Code whiche is sent from the corresponding
event, when a Telephone number which is programmed for Telemonitoring is called
with SIA Protocol (see the Listings Page): digitize the Event Code which identifies
the corresponding event, in SIA format (two letters).
The factory Event Codes appear in Table 2 at page 10.
+
The Event Codes which are programmed for Control panel Alarm, Alarm Pre-Alarm,
Control panel Warning, Control Panel Fault and Control panel Test Events, are the
same as those sent for the respective Zone Events and Network Events: Software
Zone, Conventional Zone and Network Alarms, Software Zone, Conventional Zone
and Network Pre-Alarms, Software Zone and Network, Software Zone Fault, Con-
ventional Zone and Network Warnings, Software Zone and Network Test.
Message The General Message column shows the Voice Message which is sent
by the corresponding event, when a Telephone Number which is programmed for
the sending of Voice Messages is called (see the Listings Page) : click twice on a cell
of the General Message column, to select the Voice Message you wish.
+
The selected Voice Message is linked to the Header Message and to the Status
Message. This latter depends on the type of event which gives rise to the call
(Alarm, Fault, Logical Unit Fault, Pre-Alarm, Warning, Test). See "Voice Messa-
ges" in the "General Description" paragraph for further details.
Period Test The Period Test box is used to program the parameters correspon-
ding to the Period Test, as described below.
- First Test Date and Time – Set the date and time for the first Periodic Test.
- Interval – Set the interval between two Periodic Tests: the interval may be set to a pe-
riod of between 1 and 25 hours, in steps of one hour; the default setting is 24 hours.
+
The Periodic Test event IS NOT recorded in the Events Log.
n Zones Page
The Zones page programs the parameters relating to the Software Zones. This paragraph
describes the programming of the Software Zones as relating to the Telecom Module.
Events Select the events which should give rise to the calls.
Telephone Numbers Select the Telephone Numbers which should be called by
the selected events in the Events section.
+
The Telephone Numbers from no. 1 to no. 8 could only be called by Alarm and
Pre-Alarm Events. The Telephone Numbers from no. 9 to no. 16 could only be
called by Fault, Warning and Test Events. The Telephone Numbers from no. 17
to no. 32 could be called by all events.
General Message Select the Voice Message which should be sent by the selec-
ted events in the Events section, when a Telephone Number which is programmed
to send Voice Messages is called (see the Listings Page).
+
The selected Voice Message is linked to the Header Message and to the Status
Message. This latter depends on the type of event which gives rise to the call
(Alarm, Fault, Pre-Alarm, Warning, Test). See "Voice Messages" in the "General
Description" paragraph for further details.
Event Codes When a Zones Event calls a Telephone number which is program-
med for Telemonitoring (see the Listings Page), the same Event Code which is pro-
grammed for the Control Panel Event is sent (see the Events Page):
Ø for the Software Zone and Conventional Zone Alarm event, the Event Code
which is programmed for the Control Panel Alarm event is sent;
Ø for the Software Zone and Conventional Zone Pre-Alarm event, the Event Code
which is programmed for the Control Panel Pre-Alarm event is sent;
Ø for the Software Zone Warning event, the Event Code which is programmed for
the Control Panel Warning event is sent;
Ø for the Software Zone and Conventional Zone Fault event, the Event Code
which is programmed for the Control panel Fault event is sent;
Ø for the Software Zone Test event, the Event Code which is programmed for the
Control panel Test event is sent.
n Network Events Page
The Network Events page programs the Telecom Module relating to Network
Events. The left-hand side of the Network Events page shows the information de-
scribed below for each Control Panel Network.
Ind. Shows the address of the Control Panel Network.
Control panel Shows the name of the Control Panel Network.
Description Shows the description assigned to the Control Panel Network.
On the right-hand side of the Network Events page are set the parameters relating to
the Control Panel Network selected on the left-hand side, as described below.
Events Select the events which should give rise to the calls.
Telephone Numbers Select the Telephone Numbers which should be called by
the selected events in the Events section.
+
+ The Telephone Numbers from no. 1 to no. 8 could only be called by Alarm and
Pre-Alarm Events. The Telephone Numbers from no. 9 to no. 16 could only be
called by Fault, Warning and Test Events. The Telephone Numbers from no. 17
to no. 32 could be called by all events.
General Message Select the Voice Message which should be sent by the selec-
ted events in the Events section, when a Telephone Number which is programmed
to send Voice Messages is called (see the Listings Page).
+
The selected Voice Message is linked to the Header Message and to the Status
Message. This latter depends on the type of event which gives rise to the call
(Alarm, Fault, Pre-Alarm, Warning, Test). See "Voice Messages" in the "General
Description" paragraph for further details.
Event Codes When a Network Event calls a Telephone number which is program-
med for Telemonitoring (see the Listings Page), the same Event Code which is pro-
grammed for the Control Panel Event is sent (see the Events Page):
Ø for the Network Alarm event, the Event Code which is programmed for the the
Control panel Alarm event is sent;
Ø for the Network Pre-Alarm event, the Event Code which is programmed for the
Control panel Pre-Alarm event is sent;