Mounting Instructions - Johnson Controls DP2500-R8 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 14
English
READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS CAREFULLY BEFORE
General Features
Each device has 8 jumper selectable measuring ranges. Each device is individually temperature
compensated.
Model: DP2500-R8 ( -D -AZ )
- R8 for 8 measuring range
- D for display
- AZ for autozero element
The Differential Pressure Transmitter is delivered individually packed with standard accessories
(see accessories).
Dimensions
Figure 1: Dimensions in mm

Mounting Instructions

Figure 2: Installation
ZEROING: press the button over 4 seconds
(a).
LED: long blink.....Zeroing
(b).
RESPONSE TIME CHANGE: press the button shortly
(c).
LED 3 x short blink means 0,8s selected
(d).
LED 2 x long blink means 4s selected
(e).
Figure 3: Electrical Connection
0-10 V
Output 0...10 V
4-20 mA
Output 4...20 mA
24 V
Supply 24 VAC or VDC
GND
Ground
Accessories
Standard accessories:
• 2 fixing screws
• 2 plastic duct connectors
• 2 m tube ∅ 4 / 7 mm
Optional accessories:
• Metallic duct connectors
INSTALLING AND SAVE IT FOR FUTURE USE
long term stability typical 1 year
≤ ± 1 Pa with AZ,
≤ ± 8 Pa without AZ
This document is subject to change without notice
IS_DP2500-R8 Rev. A_11 2009
Model 2500
-100...+100 Pa
0...100 Pa
0...250 Pa
0...500 Pa
0...1000 Pa
0...1500 Pa
0...2000 Pa
0...2500 Pa
1

Publicidad

Tabla de contenido
loading

Tabla de contenido