Outdoor water piping insulation
NOTICE
Outside piping. Make sure the outside piping is insulated
as instructed to protect against hazards.
For piping in free air, it is recommended to use the insulation
thickness as shown in below table as a minimum (with λ=0.039  W/
mK).
Piping length (m)
<20
20~30
30~40
40~50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool also calculates the maximum
hydronic piping length from the indoor unit to the outdoor unit based
on the emitter pressure drop or the other way around.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6

Electrical installation

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
6.1

About electrical compliance

Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
M4 (X1M)
M4 (earth)
6.3
Specifications of standard wiring
components
Component
(a)
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire sizes
EPGA11~16DAV3(7)
Daikin Altherma 3 H
4P556065-1B – 2021.09
Minimum insulation thickness
(mm)
19
32
40
50
be
reached
via
https://
EN/IEC  61000‑3‑12
(European/
Tightening torque (N•m)
1.2~1.5
EPGA11~16DAV3
30.7 A
230 V
1~
50 Hz
Must comply with applicable
legislation
Component
Interconnection cable
(b)
Recommended field fuse
Earth leakage circuit breaker
(a)
The minimum allowed field fuse is 20 A.
(b)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
6.4
To connect the electrical wiring to
the outdoor unit
1 Remove the switch box cover. See
unit" [ 4  7].
2 Insert the wiring at the back of the unit:
c
b
a
a
Power supply cable (high voltage)
b
Communication cable (high voltage)
c
Cable for bottom plate heater (optional)
3 Inside the unit, route the wiring as follows:
d
b
a
e
e
f
a
Power supply cable
b
Communication cable
c
Cable for bottom plate heater (optional)
d
Ferrite core
e
Tie strap
f
Compressor
6 Electrical installation
EPGA11~16DAV3
Minimum cable section of
1.5 mm² and applicable for 230 V
32 A
Must comply with applicable
legislation
"4.2.1 To open the outdoor
c
e
e
e
Installation manual