6 Electrical installation
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label.
2 Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
Rotating fan. Before powering ON the outdoor unit, make
sure that the discharge grille covers the fan as protection
against a rotating fan. See
grille" [ 4 11].
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Only for ERLA11~16DAV3
Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Specifications of standard wiring
components
Component
(a)
Power supply
MCA
cable
Voltage range
Phase
Frequency
Wire sizes
Interconnection cables
Recommended field fuse
Earth leakage circuit breaker
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
Installation manual
14
equivalent.
equivalent
2
"4.2.4 To install the discharge
EN/IEC 61000‑3‑12
(European/
ERLA11~16DAV
ERLA11~16DAW
3
1
30.8 A
14 A
220~240 V
380~415 V
1~
3N~
50 Hz
Must comply with applicable
legislation
Minimum cable section of 1.5 mm²
and applicable for 230 V
32 A, C curve
16 A or 20 A, C
curve
30 mA – Must comply with
applicable legislation
6.3
Guidelines when connecting the
electrical wiring
Tightening torques
Item
M4 (X1M)
M4 (earth)
M5 (X1M)
M5 (earth)
6.4
Connections to the outdoor unit
Item
Power supply cable
See
"6.4.1 To connect the electrical wiring
to the outdoor
Interconnection cable
6.4.1
To connect the electrical wiring to the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover.
2 Connect the interconnection cable and power supply (1N~or
3N~ depending on model, see name plate) as follows:
V3
1N~
1N~ 50 Hz
220-240 V
c
d
b
a
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
Tightening torque (N•m)
1.2~1.8
1.2~1.4
2.0~3.0
2.4~2.9
Description
unit" [ 4 14].
W1
3N~
OR
3N~ 50 Hz
380-415 V
L1 L2 L3
c
d
b
L1 L2 L3
N
a
ERLA11~16DAV3+W1
Daikin Altherma 3 R
4P643598-1 – 2021.09