In case you forget to confirm the changes the LCD display returns to the main
screen after 2min. without saving. Go to the next setting with the DOWN button.
Temperature hysteresis setting.
This means the fan starts to work at >25C° room temperature and reaches the
maximum speed +2C° hysteresis at 27C°. In this 2C° hysteresis from 25C°27C°
the fan is running faster and slower depending on the measured temperature.
To change the value use again SET/SAVE button to enter the setting, change
the Value with UP/DOWN button and save and return to the selection with
SET/SAVE again.
min.
20
G-Systems Engineering
What is hysteresis? Hysteresis
is the value between the lowest
and the highest point of the
regulation. Example: if we set
25C° and have a hysteresis of
2C°.
With the DOWN button you go
to the next setting "humidity
setting day time"repeat again,
enter the settings with
SET/SAVE or go to the next
setting with the DOWN button
Hysteresis setting for the
humidity day time, as described
above the hysteresis for
temperature you can change
here the controlling range for the
humidity value. For example:
10%rh at 60% humidity the fan
starts to work at 60% humidity
and +10%rh at 70%rh it reaches
its maximum speed.
Minimum speed setting day time.
Here you can choose the
minimum speed of the ventilator
which never should be undercut.