9 Quick commissioning

Quick commissioning covers only the basic and motor-specific settings. Application-specific settings must
be made based on the manufacturer's documents.
See: Parameter List User Documentation:
Siemens document number: 6SE6400-5BA00-0AP0
Device operation is described in the following manufacturer documentation:
Micromaster 420 operating instructions:
Siemens document number: 6SE6400-5AA00-0AP0
Parameter
Value range/setting
number
P0003
Access level
0 User-defined parameter list
1 Standard: access to the most frequently used parameters
2 Advanced: Advanced access, e.g. to frequency converter I/O functions
Commissioning parameters
P0010
0 Ready
1 Quick commissioning
P0100
Europe / North America
0 Europe [kW] , standard frequency 50 Hz
P0300
Selection of motor type
1 Asynchronous motor
P0304
Nominal motor voltage
P0305
Nominal motor current
P0307
Nominal motor power
P0700
Command source selection
2 Terminal strip
P1000
Frequency setpoint selection
2 Analog setpoint
sP1080
Min. speed
0...5.00 Hz...650 Hz
Max. speed
P1082
0...150.00 Hz...650 Hz
P1120
Ramp-up time
0...10 s...650 s
P1121
Ramp-down time
0...10 s...650 s
P3900
End of quick commissioning
0 (resets commissioning parameter P0010 to 0)
See the manufacturer's documents for other setting options.
© Festo Didactic 8036953
3-phase
3-phase
asynchronous motor
asynchronous motor
Order no.: 571874
Order no.: 571874
Star operation
Delta operation
400 V
230 V
0.76 A
1.32 A
0.25 kW
0.25 kW
MPS® transfer
MPS® transfer
section MT AC
section MT AC
Order no.: C93102
Order no.: C93102
Star operation
Delta operation
400 V
230 V
0.1 A
0.17 A
0.022 kW
0.026 kW
33