Heat transfer problems
The heat transfer capacity is dropping.
Measure temperatures at inlets and outlets. Also
measure flow rates on both media, if possible. At
least on one of the media, both temperatures and
the flow rate must be measured.
• Check to see if the transferred amount of
heat energy corresponds to the
specifications.
• If great precision is important, it will be
necessary to use laboratory thermometers
with an accuracy of 0.1 °C, and also to use
the best equipment available for flow
measurement.
Has the heat transfer capacity of the unit dropped
below specified values?
RU
16
All manuals and user guides at all-guides.com
Поиск неисправностей
Action
Result
YES
Clean the heat transfer surface.
Use the Cleaning-In-Place (CIP)
system.
NO
–
Пластинчатый теплообменник
Correction