ETM
Adjustment
- for output function
Attention:
Do not change the distance to the detecting object or the filling level during the adjustment
The two switching points S1 and S2 can be adjusted independently of each other. That means, that after
changing one of the switching points, there is no new adjustment necessary for the other switching point.
These adjustments must always be made with the detected product (adjustment "full").
Adjustment switching point 1 (S1)
• The active surface of the sensor must be covered completely with the product to be detected or the
product must be in the desired position.
• Hold the teach magnet on the EasyTeach spot until the LED flashes green (see EasyTeach-Chart).
• Remove teach magnet.
• During the initialization process the LED flashes green with higher frequency.
The adjustment S1 is finished when the LED is static yellow. The switching point S1 is now optimally
adjusted for the detection of the product currently being used and the current mounting conditions.
The switching hysteresis is calculated automatically.
Adjustment switching point 2 (S2)
• The active surface of the sensor must be covered completely with the product to be detected or the
product must be in the desired position.
• Hold the teach magnet on the EasyTeach spot until the LED flashes yellow (see EasyTeach-Chart).
• Remove teach magnet.
• During the initialization process the LED flashes yellow with higher frequency.
The adjustment S2 is finished when the LED is static yellow. The switching point S2 is now optimally
adjusted for the detection of the product currently being used and the current mounting conditions.
The switching hysteresis is calculated automatically.
Test function
The test function can be used to check that the sensor is connected correctly.
• Hold the teach magnet on the EasyTeach spot until the LED flashes green and yellow at the same
time (see EasyTeach-Chart).
The test function switches the output A1 and A2 ON and OFF at the same time. The test function is
activated until you remove the EasyTeach magnet. The adjusted values stay unchanged.
Maintenance, repair, disposal
• Maintenance for this device is not necessary when used as intended.
• It is not possible to repair the device. If you have any problems, please contact directly your customer service.
• Please dispose of the device in a way that is environmentally friendly according to the national regulations
2 x Normally Open / 2 x Normally Closed
27