Heater and stand location
- The heater is primarily for outdoor use only. Always ensure
that adequate fresh air ventilation is provided.
- Always maintain proper clearance to non protected combus-
tible materials i.e. top 100 cm and sides 100 cm minimum.
- Heater must be placed on level firm ground.
- Never operate heater in an explosive atmosphere like in
areas where gasoline or other flammable liquids or vapors are
stored.
- To protect heater from strong wind, anchor the base securely
to the
Gas requirements
- Use propane, butane or their mixtures gas only.
- The pressure regulator and hose assembly to be used must conform to local stan-
dard codes.
- The installation must conform to local codes, or in the absence of local codes, with
the standard for the storage and handling of liquid petroleum gases.
- A dented, rusted or damaged tank may be hazardous and should be checked by
your tank supplier. Never use a tank with a damaged valve connection.
- The tank must be arranged to provide for vapor withdrawal from the operating
cylinder.
- Never connect an unregulated tank to the heater.
Leakage test
Gas connections on the heater are leak tested at the factory prior to shipment. A
complete gas tightness check must be performed at the installation site due to
possible mishandling in shipment or excessive pressure being applied to the heater.
- Make a soap solution of one part liquid detergent and one part water. The soap
solution can be applied with a spray bottle, brush or rag. Soap bubbles will appear
in case of a leak.
- The heater must be checked with a full cylinder.
- Make sure the safety control valve is in the OFF position.
- Turn the gas supply ON.
- In case of a leak, turn off the gas supply. Tighten any leaking fittings, then turn the
gas supply on and recheck.
- Never leak test while smoking.
14
Egypt
Ceiling
100 cm
Fig.4. Distance security