Electrical Wiring - Rd1 - Toshiba RBC-RD1-PE Instrucciones De Instalación

Ocultar thumbs Ver también para RBC-RD1-PE:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 37
All manuals and user guides at all-guides.com
K7046 Combined Installation
Electrical Wiring – RD1
G
There are various options when installing a RD1 unit, firstly it can be installed as a
stand alone unit. Secondly it can be installed with any AI indoor unit ('4' Series and
MMS indoors), this will enable fault codes to be generated and the indoor unit can be
shut down. Thirdly solenoid valves can also be installed as an optional extra.
G
Ensure that the control unit is protected with a 1A 240VAC fuse.
G
The maximum rating of the solenoid relay is 240V~ 5A.
G
It must be noted that any solenoids valves selected for this application must be
capable of operating at a pressure of 33bar and with the flow being bi-directional.
G
If rear entry is required, Ø16mm holes can be made in the rear of the control box.
Centre marks for the holes are provided.
Remote Sensor
Assembly
TOP
TOP
+
Sig
Buzz
MAKE
COM
+ sig – mute + buzzer
6/3/01
8:37 am
Page 11
GB
Indoor Unit
PCB
RAV = CN17
MM = CN21
Solenoid Valves
2 Core
(Optional)
Cable
(Supplied)
Volt Free Relay
Contacts
Max Rating
240V~5A
230V 50Hz
1A Supply