K7046 Combined Installation
The function of the jumpers are listed below:
Jumper
RBC-RD1-PE
A
Not Used
B
Not Present
C
Not Used
JP
Disable unit shutdown
AJP
Close Alarm contacts
BJP
Present
From the above the only jumpers which are user selectable are "JP" and "AJP".
G
JP: If this jumper is removed the indoor unit or outdoor system will not shutdown
(hence B6 – indoor, and 04 – outdoor fault codes would not be generated). Removing
this jumper is not recommended unless it is critical that the system must remain
operating.
G
AJP: If this jumper is fitted, then the Alarm (Solenoid valve relay) contacts are closed.
This is not depended on the unit being powered. The primary reason for this jumper is
during commissioning. If valves are fitted, then the air conditioning system can run,
even when the detector is not commissioned or powered.
G
All other jumpers must be fitted as shown in the table for correct system operation.
6/3/01
8:37 am
Page 7
GB
Unit Setup
RBC-RD2-PE
Not Used
Present
Not Used
Disable unit shutdown
Close Alarm contacts
Not Present
7