Ketra HW-X96-X-J1 Guia De Instalacion página 10

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

I N S TA L L AT I O N
Troubleshooting
Ketra's LS0 Linear should power on to a default white state. If it powers on to some other color, that
means there's a problem in the installation conditions. See the table below for the meaning of each color.
T R O U B L E S H O OT I N G TA B L E
Color
Condition
Red or OFF
Voltage from X96 controller is
too low
Magenta
LS0 is installed backwards
Blue
Missing or reversed
communication signals
Green or OFF
Line voltage is too low
Yellow
Number of luminaires exceeds
length limits. Limit for 15 ft
(4.6 m) for high output and
diffused lens type and 24 ft
(7.3 m) for long run lens type.
10 | X96 INSTALLATION GUIDE
Correction
Ensure that the controller is the Ketra X96 controller.
Check to see if total cable length exceeds 50 ft (15 m),
reduce to 50 ft (15 m) of cable from X96 to last LS0
segment. Ensure that power conductors are 16 AWG
(1.5 mm
) wires, or use the QSH-CBL(P)-M-500 or
2
QSH-CBL(P)-L-500. Ensure that length of LS0 linear
does not exceed maximum length requirements i.e.,
15 ft (4.6 m) for high output and 24 ft (7.3 m) for long
run. Verify power connections (red and black on QSH-
CBL-M-500) are wired correctly on the X96 controller
and each luminaire adapter
Disconnect power, check wiring at adapters and follow
wiring directions above, or disconnect luminaire and
reverse direction
Verify communication (purple and white on
QSH-CBL-M-500) are wired correctly on the
X96 controller and each luminaire adapter
Line voltage must be nominally 120 or 277 V~
60 Hz for X96
Remove excess luminaires and power cycle the
X96 controller
P/N 3662641 Rev A
© 2021 Lutron Electronics Co., Inc.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cm-x96-x-j1

Tabla de contenido