Defrost; Maintenance - Nordcap APKTM 2T Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 33
Possible configuration for HACCP control on the Powercompact controllers ( each user must programm the controller
according to the specifications defined by him for each unit):
St = 0
rd =3
AH =8 (the HI alarm trips at 8+3 =11ºC)
AL =3 (the LO alarm trips at 3-3º=0ºC)
Ad = 30 (30 min delay on the alarms)
tc = Date and time
Htd=45 (45 min after the alarm being tripped the HACCP begins to record)
The records are made on the following parameters:
HA, HA1, HA2 or HF, HF1, HF2– day of the last HA or HF event
The reset of the alarms are done by pressing the HACCP key and then by pressing the continuous cycle key ( the draft
up ) at the same time. You must press both keys for 5 seconds.

4.4 - Defrost

The table defrosts automatically.
It is advisable that after the defrosting the doors should not be opened so as to allow the temperature level to be reached more
rapidly.
The defrost and condensation water run into a pan placed in the refrigeration group, where they are automatically evaporated.
4.5 - Cleanliness
In order to ensure perfect hygiene and conservation, it is recommended that the following regular and daily cleaning procedures
are adhered to:
Careful and regular cleaning of the surfaces using damp clothe.
A neutral detergent and water should be used, totally avoiding those that are chlorine-based or are abrasive.
Wash down with pure water and dry with care.
The use of water-pressure jets is not recommended, in particular in the direction of the compressor.
Cleaning of the drainage tables is recommended and verification of the existence or not of items or residue that may obstruct
the flow of the condensation water.

4.6 - Maintenance

In order to ensure long life and correct operation of the refrigeration system, regular maintenance of the condensation should be
carried out, as follows:
Disconnect the cupboard from the electric current, by taking out the plug.
Vacuum or lightly brush the condensation, according to the track direction.
MNS00024_03
TEC
INSTRUCTIONS MANUAL
St
Year, month, day, day of the week, hour and
minutes when programming
N.º
MNS00024_03
HI = AH + St
rd
13/45

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

46710110001-0-n-t

Tabla de contenido