Installation Instructions - WeatherProof Wire Connectors:
Model 61, 62 & 63
• Do not exceed the rating of these connectors
• Turn OFF power before removing or installing connectors
• Wiring must comply with all applicable electrical regulations
• COPPER TO COPPER ONLY. Do not use on aluminium wire
• Incorrect use of these connectors can cause electrical fires, personal injury or death
• Strip wires back to required length - refer to table.
• Straighten wires and align frayed strands.
• Hold wires together with ends even. Lead stranded wires slightly ahead of solid wires.
• Pre-twisting acceptable, but not required. When pre-twisting, strip wires long, hold wires together
with insulation even, twist wire ends together, trim conductors to recommended strip length
• Hold wires firmly, insert wire bundle into connector and twist clockwise until tight
Ratings & Wire Size Combinations for WeatherProof Wire Connector
Model
Colour
61
Grey/Orange
62
Grey/Red
63
Grey/Blue
Strip Length
Rating
10 mm
24A/450V
16 mm
32A/450V
16 mm
32A/450V
www.idealind.com
1.5 mm
2
IP Rating
Min
Max
IP55
1
2
IP55
2
6
IP55
n/a
n/a
2.5 mm
4.0 mm
2
2
Min
Max
Min
Max
1
2
n/a
n/a
1
5
1
4
3
6
2
6
1/5

Publicidad

loading

Resumen de contenidos para Ideal 61

  • Página 1 Installation Instructions - WeatherProof Wire Connectors: Model 61, 62 & 63 • Do not exceed the rating of these connectors • Turn OFF power before removing or installing connectors • Wiring must comply with all applicable electrical regulations • COPPER TO COPPER ONLY. Do not use on aluminium wire •...
  • Página 2 Installationshinweise - WeatherProof Drahtverbinder: Modelle 61, 62 & 63 • Halten Sie die Bemessungswerte der Verbindungsklemmen ein. • Schalten Sie den elektrischen Strom ab, bevor Sie diese Verbindungsklemmen ein- oder ausbauen. • Die Leitungsführung muss allen geltenden Vorschriften für Elektroinstallationen entsprechen •...
  • Página 3 Instructions de montage - Connecteur WeatherProof Modelès 61, 62 & 63 • Ne dépassez pas les ampérages de ces connecteurs • Coupez l’alimentation avant le montage ou le retrait de ces connecteurs • La câblage doit être conforme à toutes les réglementations électriques •...
  • Página 4 Instrucciones de instalación - Conectores WeatherProof Modelos 61, 62 & 63 • No superar la potencia nominal de los conectores • Apague la alimentación antes de instalar o quitar conectores • Los cables deben cumplir con todas las normativas eléctricas aplicables •...
  • Página 5 Instrukcje instalacji - Złącza WeatherProof Modele 61, 62 i 63 • Nie przekraczać wartości znamionowych złącz. • Przed montażem lub demontażem tych złącz należy wyłączyć zasilanie • Przewody muszą być zgodne ze wszystkimi obowiązującymi przepisami elektrycznymi • TYLKO DO ŁĄCZENIA MIEDZI Z MIEDZIĄ. Nie używać w przypadku aluminium.

Este manual también es adecuado para:

6263