Service Tasks; Calibrating The Oil Scales (For Asc2300G/Asc3000G Only) - Waeco AirConServiceCenter ASC1300G Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Service tasks

9
Service tasks
9.1
Calibrating the oil scales
(for ASC2300G/ASC3000G only)
I
NOTE
In order for the oil quantities and the UV additive to be measured
correctly, the zero point of the scales must be checked regularly and
reset if necessary.
Resetting is necessary:
 If the quantity in a container deviates by more than 10 ml from the
target value
 If the AirConServiceCenter has been shaken, for example during
transport on bumpy roads
 Every four to six weeks
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor keys  or  to select "Reset scales":
✓ You are then prompted to remove the containers from the scale:
102
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Remove the 3 Oil/UV
glasses from scales.
ENTER-OK STOP-EXIT
AirConServiceCenter
EN

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Airconservicecenter asc2300gAirconservicecenter asc3000g

Tabla de contenido