Three phase operation (see appendix D)
Step 1: Setting ds2 and ds1 for 3-phase operation
Leader (L1)
DS-8 AC-in-1
Set
DS-7 AC-in-1
Set
DS-6 AC-in-1
Set
DS-5 AC-in-2
Set
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Leader
on
DS-1 Leader
As the table above shows, the current limits for each phase should be set separately (ds8 thru ds5). Thus, for AC-in1 as well as
AC-in-2, different current limits per phase can be selected.
If a panel is connected, the AC-in-2 current limit will equal the value set on the panel for all phases.
The maximum charging current is the same for all devices, and should be set on the leader (ds4 and ds3).
Example:
AC-in-1 current limitation on the leader and the followers: 30A (setting for generator power 30 x 120 x 3 = 11kVA).
AC-in-2 current limitation with 16A panel.
If the charging current on the leader is set to 100% (70A for a Quattro 48/5000/70-100/100) and the system consists of three
devices, then the effective system charging current is equal to 3 x 70 = 210A.
The settings according to this example (15kVA 3-phase system) are as follows:
Leader (L1)
DS-8 AC-in-1
30A
DS-7 AC-in-1
30A
DS-6 AC-in-1
30A
DS-5 AC-in-2 na (16A panel)
DS-4 Ch. current 3x70A
DS-3 Ch. current 3x70A
DS-2 Leader
DS-1 Leader
To store the settings after the required values have been set: press the 'Up' button of the leader for 2 seconds (upper button to
the right of the DIP switches, see appendix A, position K). The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
20
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 Set
DS-4 na
DS-3 na
DS-2 Follower 1
off
DS-1 Follower 1
Follower (L2)
off
DS-8 AC-in-1 30A
on
DS-7 AC-in-1 30A
on
DS-6 AC-in-1 30A
DS-5 na
on
DS-4 na
on
DS-3 na
on
DS-2 Follower 1
off
DS-1 Follower 1
Follower (L2)
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 Set
DS-4 na
DS-3 na
off
DS-2 Follower 2
off
DS-1 Follower 2
Follower (L3)
off
DS-8 AC-in-1 30A
on
DS-7 AC-in-1 30A
on
DS-6 AC-in-1 30A
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Follower 2
off
DS-1 Follower 2
Follower (L3)
off
on
off
on
on
off
on