seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
Lights will not turn OFF:
• Cut Off time may be set to "None."
• Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor's view for that time period when
the lights are in Low Mode.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after
5 seconds, and the OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
There is no communication with the Sensor Config App:
Perform a power cycle on the FSP-321.
The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm up time if
no motion is detected.
Catalog #
FSP-321
Digital Continuous Dimming PIR Fixture Integrated Sensor with Bluetooth
FSP-L2
360° lens, up to 44' diameter at 8' height
FSP-L2-S
360° lens, up to 44' diameter at 8' height, with shroud
FSP-L3
360° lens, up to 40' diameter at 20' height
FSP-L3-S
360° lens, up to 40' diameter at 20' height, with shroud
FSP-L7
360° lens, up to 100' diameter at 40' height
FSP-L7-S
360° lens, up to 100' diameter at 40' height, with shroud
FSP-C1
Small collar, for use with FSP-L2 and FSP-L3 lenses
FSP-C2
Large collar, for use with FSP-L7 lens
Sensor is White.
OPERATION DURING POWER-UP

ORDERING INFORMATION

4
Description

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fsp-321

Tabla de contenido