No: 24051 – 10/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: CI-205
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
The CI-205 is a 24VDC Passive Infrared (PIR) occupancy sensor which controls lighting or HVAC systems based on occupancy in a
given area.
PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them, so careful consideration must be given to sensor placement.
The CI-205 has a multi-cell, multi-tier Fresnel lens with a field of view of 360°. The sensor has two lens pattern options. The Extended
Range Lens will cover up to 1200 sq ft when mounted from 8-12 ft. The High Density/Reduced Range Lens will cover up to 500 sq ft
when mounted at 8-12ft.
Coverage shown in the diagrams below is maximum and represents coverage for half-step walking motion, with no barriers or obstacles
Top View @ 8ft
Extended Range Lens (Standard) CI-200
8 ft
2,4m
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
Side View
6,7 m
The effective coverage distances may be slightly less than the maximum sensing distance (see Coverage Patterns), depending upon
obstacles such as furniture or partitions, and this must be considered when planning the number of sensors and their positioning. See
the list for approximate coverage distances for different types of motion.
UNIT DESCRIPTION
COVERAGE PATTERNS
13 ft
7 ft
3 ft
0 3 ft
7 ft
13 ft
4m
2,1m
1m
1m
2,1m
4m
Wattstopper
360° Passive Infrared • Low Voltage Occupancy Sensor (version 2)
IRP 360 ° • Détecteur de présence de basse tension (v2)
Pasivo infrarrojo de 360° • Voltaje bajo Sensor de ocupación (v2)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage ................................................20-30VDC (24VDC Typical)
Current Consumption ...........................@24VDC, 24mA Maximum
Isolated Relay Rating ................................1A @ 24VDC or 24VAC
Operating Temperature ........................ 32°F to 131°F (0° to 55°C)
Time Delay Adjustment ............................. 15 seconds-30 minutes
PIR Coverage
Model CI-205 ..............................................................up to 1200ft2
Model CI-205-1 ............................................................up to 500 ft2
Light Level Adjustment ......................................................1-190FC
Sensitivity Adjustment ..................................... Minimum-Maximum
UL & CUL Listed
Top View @ 8ft
High Density/Reduced Range Lens CI-200-1
22 ft
Side View
6,7 m
PLACEMENT
®
SPECIFICATIONS