• Technical characteristics
Case
Dimension (w x h x d)
Connections
Degree of protection
Weight:
Display
Type:
Auxiliary supply
Value Uaux ac:
Measurement
Three-phase 3 and 4-wire network
Voltage (TRMS)
Direct measurement
Three-phase rated voltage Un:
Power consumption voltage circuit:
Voltage accuracy class:
Current (TRMS)
Direct measurement
Curren accuracy class:
Short-time overcurrent
(IEC/EN 62053-21, IEC/EN 62053-23):
Frequency
Rated frequency
Permitted variation
Energies
Active energy accuracy class:
Reactive energy accuracy class:
36
LE11865AA.indd 36
LE11865AA.indd 36
71,2 x 90 x 65mm
80...500 V~ (Phase - phase)
U
50...290 V~ (Phase - Neutral)
MAX
8 mm
1 x 2,5 mm
1 x 2,5 mm
1 x 4 mm
I = 0,5 A I = 10 A I
min
n
I = 1 A I = 20 A I
n
min
MKD4R63FC001 - MKD4R63DT - MKD4R63MT
Front face IP54, Terminals IP20
0000-00-0000
MKD4R125FC001 - MKD4R125DT - MKD4R125MT
MKD4R63FC001
230 gr.
MKD4R63DT - MKD4R63MT
I
MKD4R125FC001
MKD4R63FC001 - MKD4R63DT - MKD4R63MT
250 gr.
0000-00-0000
MKD4R125DT - MKD4R125MT
MKD4R125FC001 - MKD4R125DT - MKD4R125MT
Backlighted LCD display
230V ± 15%
350 mm
Wh(E
):1 (IEC/EN 61557-12)
a
cl
varh(E
):2
(IEC/EN 61557-12
rv
(-25°C ) - (55°C)
3x230V~ / 3x400V~ ± 15%
Max. 1,5VA three-phase
0,5
MKD4R63FC001
I
min
MKD4R63DT - MKD4R125DT
MKD4R125FC001
I
min
MKD4R125DT - MKD4R125DT
1
30 I
/ 10ms
max
F
50Hz; 60Hz
n
49...51 Hz, 59...61Hz
1 (EN 61557-12)
2 (EN 61557-12)
CAT III
max. 0,6 Nm
2
2,5mm PH0
2
2
= 63 A
max
= 125 A
max
1,5...10 mm
2
/ Ø 4,8 mm
M
AX
1,5...16 mm
2
/ Ø 4,8 mm
16...50 mm
/ Ø 6,4...12,4 mm
2
M
AX
25...70 mm
/ Ø 6,4...12,4 mm
2
16 mm
/ Ø 9,3 mm
2
25 mm
2
/ Ø 9,3 mm
50 mm
/ Ø 15,3 mm
2
70 mm
2
/ Ø 15,3 mm
)
0,5A - I
10A - I
63A
n
max
1A - I
20A - I
125A
n
max
03/03/20 15:46