Bradley SN2003/IR Manual Del Usaurio página 10

Ocultar thumbs Ver también para SN2003/IR:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SN2003/IR, SN2023/IR
Troubleshooting – Solenoid Valve
Turn off water supplies to the
unit before troubleshooting.
Item
Qty.
Part No.
1
1
118-307
1
1
118-307A
2
1
269-983
3
1
269-577
4
1
269-578
5
1
269-1729
6
1
269-1730
7
1
269-579
8
3
160-447
9
1
125-165
10
1
110-231
Problem
Cause
An individual
Debris is
operating
trapped
station fails
between the
to shut off
diaphragm
and drips .
and the valve
seat .
An individual
A failed coil for
operating
the valve or
station fails
loose electrical
to turn on .
connection to
the terminal .
10
S65-113
Description
Valve Body, 1/4" Closed
Valve Body, 1/4" Thru
Diaphragm
Armature
Spring
Armature Housing
Clamp, Armature
Housing
Coil, Solenoid Valve
Screw, #8 x 5/8
O-Ring, #2-013
Compression Nut 1/4"
Tube
Remove debris between diaphragm and the valve seat .
1 . Remove the three #8 Phillips-head screws that hold the solenoid valve assembly together . Be
careful not to lose the armature or spring .
2 . Remove the diaphragm . Remove any particles that have been trapped between the diaphragm
and the valve seat . Rinse off the diaphragm and inspect for damage . Make sure the center
orifice and both small side orifices are open .
3 . Reassemble in reverse order (do not overtighten the Phillips-head screws or the plastic valve
body may crack) . Tighten until the armature plate makes contact with the plastic body .
4 . Reconnect the wiring .
Test the station to determine the cause .
1 . Disconnect the wires from the coil of an adjacent valve . Disconnect the wires from the problem
valve and reconnect to the adjacent valve .
2 . Turn on electrical and water supplies to the unit . Pass your hand in front of the sensor of the
problem station, and the adjacent station should turn on .
3 .
If the adjacent station turns on and cycles normally, replace the coil on the problem valve .
If the adjacent valve fails to turn on, inspect the wires from the sensor cable and do the following:
• make sure there are no breaks and that the fully insulated disconnect terminals are firmly
crimped in place;
• turn off the electrical and water supplies;
• reconnect to the adjacent valve and turn on the water supplies to the unit;
• pass your hand in front of the sensor . If the station still fails to turn on, replace the sensor .
9/5/2014
Repair Kits
S07-067
S07-067A
(Closed
(Thru
Body)
Body)
-
X
-
-
-
X
X
X
X
X
X
X
X
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
-
-
Solution
8
7
8
9
Bradley • 215-1073 Rev. L; ECN 14-00-007
Installation
6
5
4
3
2
1
10

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sn2023/ir

Tabla de contenido