Reading Command Examples; Modbus Rtu/Ascii - Algodue ELETTRONICA UPM309 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. READING COMMAND EXAMPLES

In this chapter, some reading command examples are described according to the used communication protocol
(RTU/ASCII or TCP).

5.1 MODBUS RTU/ASCII

The following tables show some reading examples in MODBUS RTU.
Values contained both in Query and Response messages are in hex format.
CURRENT VALUE READING
Query example: 0103000E000A0EA4
Example Byte Description
01
-
Slave address
03
-
Function code
00
High
Starting register
0E
Low
00
High
10 words to be read
0A
Low
0E
High
CRC
A4
Low
Response example: 010314000009990000099F000009900000001900000998C070
Example Byte Description
01
-
Slave address
03
-
Function code
14
-
20 data bytes
00
High
00
Low
2457 mA phase 1 current (A1)
09
High
99
Low
00
High
00
Low
2463 mA phase 2 current (A2)
09
High
9F
Low
00
High
00
Low
2448 mA phase 3 current (A3)
09
High
90
Low
00
High
00
Low
25 mA neutral current (AN)
00
High
19
Low
00
High
00
Low
2456 mA system current (A∑)
09
High
98
Low
C0
High
CRC
70
Low
88