WARNING
!
Hazardous voltages are present in certain parts of this electrical equipment during operation.Incorrect handling of the
equipment can result in death, severe personal injury or substantial property damage. Only qualified personnel are allowed
to work on or around this equipment. The successful and safe operation of this equipment is dependent on proper transport,
storage and installation.
Before installation or maintenance work is carried out, the mains switch must be switched off and locked to prevent it from
being switched on again. If these rules are not adhered to, contact with live parts or improper use can result in death or
severe personal injury.
CAUTION
The device may only be opened by qualified personnel. Electrostatically sensitive devices (ESD)
Description
The additional module for redundant mode of 2 supplies is a built-in device belonging to the SITOP series.
The device must be installed taking into account all relevant DIN/VDE specifications and other national standards.
It is used in combination with two stabilized 24V load power supply units to implement a redundant 24V supply. If one of the power supplies
fails, the other will supply the load.
For this purpose the redundance module is connected in parallel mode with the SITOP load power supply units. The "In 24V-1" and "In
24V-2" inputs of the redundance module must be connected to the "+" outputs of the power supply units, and the "Gnd" input of the
redundance module to the "-" outputs of the power supply units. The "Out 24V" output must be connected with the load (see wiring
information on page 2). The output cable of the redundance module must be wired with the same conductor cross-section as the output
cables of the power supplies.
The failure of one of the 24V power supplies will be signalized via an LED and a relay contact. The response threshold of this signaling
system can be set using a potentiometer on the redundance module in the range from 20V to 25V.
!
Caution: The redundance module is suitable for the redundant setup of two SITOP power supplies up to a rated output current of 20A
each! For the redundant setup of 2 power supplies with 30A or 40A rated output current, two redundance modules will be necessary. In
this case one redundance module is assigned to one power supply respectively and the terminals "In 24V-1" and "In 24-2" need to be
interconnected on each module.
Technical data
Input variables
Rated input voltage U
:
e
24V DC
Operating voltage range:
22...28.8V DC
Output variables
Output DC voltage U
:
a
U
– approx. 0,5V
e
Output DC current I
:
a
0...40 A
Max.Output sum current I
:
a
40A
Installation
Mounting on a DIN EN 50022-35x15/7.5 standard rail. To ensure adequate cooling, the device must be installed vertically, with the
terminals at the bottom. Be sure to leave a minimum clearance of 50mm above and below the device.
Connections and terminal assignment
Terminals
Function
In 24V-1
Max. output summation current :
In 24V-2
Input 24V supply voltage from power supply 2
Out 24V
Output 24V supply voltage to the load
Gnd
0V connection to the internal supply
ok
Floating relay contact (changeover contact)
SIEMENS AG ÖSTERREICH, 12.2003
Signaling
Green LED:
both Input voltages > switching threshold
Red LED:
at least one input voltage < switching threshold
Floating relay contact:
message o.k. if both Input voltages > switching threshold,
contact rating: 6 A / 240 V~
Setting range of threshold:
20V ± 0.5V... 25V ± 0.5V
Ambient
Temperature
Storage and transport: -25 to +85°C [-13 to 185°F]
Operation:
0 to +60°C [32 to 140°F]
4/ 8
Humidity rating corresponds to climatic category
3K3 acc. to EN 60721 Part 3, no condensation
Natural air cooling
Specifications
Degree of protection: IP20 acc. to IEC 529
Safety class 1 acc. to IEC 536
Safety acc. to VDE 0160 and VDE 0805
(EN 60950): SELV
Emitted interference acc. to EN 50081-1
Radio interference suppression acc. to EN 55022,
limit curve B
Noise immunity acc. to EN 61000-6-2, ENV 50204
UL 508 in preparation
Weight
1,0kg [2,2 lb.]
Terminal range
Remarks
2
0.33 to 10mm
Screw-type terminals. Use a screw driver with a
[AWG 22 to 8]
blade width of 5mm. Recommended tightening
torque 1,2Nm.
2
0,5 to 2,5mm
Screw-type terminals. Use a screw driver with a
[AWG 24 to 12]
blade width of 3mm. Recommended tightening
torque 0,5...0,6Nm