Technical Data - CEAG COOPER Crouse-Hinds AB 12 108 EVG Serie Instrucciones De Uso

Luminarias de emergencia para atmósferas explosivas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
¡The luminaires must not be operated in
Zones 0 and 20!
¡The tecnical data indicated on the
luminaires are to be observed!
¡Changes of the design and modifications to
the luminaires are not permitted!
¡The luminaires shall be operated as
intended and only in undamaged and
perfect conditions!
¡Only genuine Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
spare parts may be used for replacement!
¡Repairs that affect the explosion protection,
may only be carried out by
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
ouse-Hinds, S.A. or a qualified
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
"electrician" and will subsequenctly have to
be cheked by an "expert"!
Do not keep these operating instructions
inside the luminaire during opertion.
¡The national safety rules and regulati-
ons for prevention of accidents and the
following safety instructions which are
marked with an (
) in theses operting
instructions, will have to be observed!
2. Conformity with standards
This explosion protected luminaires meets the
requeriment of IEC/EN 60079-1, IEC/EN 61241-1
and EN60598-2-22. It also complies with the EC
Directives for"Apparatus and protective
systems for use in explosive atmospheres"
(94/9/EC) and "Electromagnetic compatibility"
(89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in explosive
atmospheres,Zone 1 and 2 acc. to IEC60079-10. and
Zones 21 and 22 acc. IEC 61241-10.

3. Technical data

Applications
II2GD
Class I
Exd IIC T6
Class II
Ext
1)
A21 IP 67 T85ºC
Certificates
LOM 02 ATEX 2013X
Others, contact us
Type:
AB 12 108 EVG
2)
Lamps to be use
:
8W / T16, 450lm
Lampholder
G5 ; EN60061-2
Approval of the production
ATEX Quality assurance: LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
o
Temperature of use:
-20
C to + 40
Version CG
-DIRECTA or TROUGTH
CEA GUARD SYSTEM
connection
-Rated voltage:
230V 50/60Hz
220V DC + 25/-20%
-Rated current
(220V batteria):
30mA
-Power conssumption
16VA
-Single luminaire
monitoring wit switch for: 20 adresses
Version 24V DC
-DIRECT connection
-Rated voltage:
24V DC +25/-15%
-nominal current
350mA
Notes:
1) Installe in areas without mechanical risk, due the nomal operation in the industrial processe.
2) Includend in the supplying
Material of enclosure:
Material of glass
Storage temperature in
original Packing
Terminals capacity:
Entries of cables
Direct entry:
Dimensions:
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of explosi-
on protected apparatus will have to be observed.
Transport and storage of the luminaire is
permitted in original packaging only!
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions!
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the cover is
completly threaded on the luminaire enclosure!
¡See secuency in figure 2!
Dimensions for mounting:
Accesories for mounting:
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
See Cooper Cr
Cooper Cr
Cable entries
Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type
and dimensions of the main conection cable,
following their manufacturer instructions.
¡The cable entries devices has to be the
protection mode Exd!
Unused cabe entries have to be closed by a
correspondante certified Exd blanking plug.
If the original blanking plugs are used , these
must be tightened with 15 Nm torque.
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps for
1)
the supplied luminaire. See indications in the
general label of the luminaire and in the present
instructions!
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions and
o
C
others applicable regulations!
Only carry out insulation measurements between PE
and external conductor (L1,
-
and (N,
).
λ
-
=1
-
Then the luminaire have to be tightly closed.
Metal aloy aluminium
without Cu,painted
polyester grey.
Borosilicate
-40
o
C a + 60
o
C
2
2 x 2 x 2,5mm
PE ext.: 2 x 6mm
2 x ¾" ISO 7/1,
one plugged
See figure 1.
See figure 1
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. catalogue
ouse-Hinds, S.A.
See wiring diagram.
+
) as well as between PE
measurement voltage: max. 1kV AC/DC
min. insulation: 2 MΩ
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive atmospheres,
as well as the general rules of engineering!
¡For dust explosive application, pay special
attention dont't have present clust layers abore
2
5mm on side of the apparatus!
Servicing
¡The responsable of the safe use of these
apparatus is the property!
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas and blanking plugs for their firm fix.
Lamp replacement in acc. with the
manufacturer instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure
it protection in front of the corrosion, water
ingrees and seize-up problems. Cleaning rest of
greasse and corrosion no using sharp metallic
devices who can damage the surface of the joint,
and greasing they using apropiate greasse
thermically and chemically stable like e.g.:
    
Molikote
BR2 plus.
¡When the housing need to be repeinted, pay
attention that the flameproof joints rest without
tracks of coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires have
to be disconnected from the main conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of repairing have to be
made by "qualified" personnel!
¡The reparation of the sealed part between the
housing the glass have to be done by
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.!
ouse-Hinds, S.A.
¡ The users are not authorized to repair this sealed
part!
¡All reparations have to be done without voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated in
IEC 79-19.
¡Only use genuine Cooper Cr
spare parts!