Both Room Controllers communicate to all other DLM devices connected to the DLM Local Network. Connections shown are for
example only. The low voltage LMRJ cables can connect to any DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG. For the LMRC-213, each relay is rated for up to 20A; total load not to exceed 20A. For the
LMRC-213-347 each relay is rated for up to 15A; total load not to exceed 15A. Specified load types can connect to any load relay.
Do not connect different load types to the same relay. For dimming ballasts or drivers, connect the 0-10V control wires to the 0-10V
terminals that match the load relay output connection.
Corner Mount
Sensor
Switch
The room controller mounts as the cover for a four square deep junction
box. After connecting the load and line wires, secure the LMRC-213 to the
cover tabs on a deep junction box using two screws.
J-Box
Cover a 4"x 4"x 2 1/8"deep
(minimum) box.
Plug n' Go supports the most energy efficient control strategy.
For example, if at least two loads, one switch and one occupancy
sensor are connected to the DLM local network, the system
operates load A as Automatic ON, Automatic OFF and load B as
Manual-On, Automatic-Off.
See DLM device Quick Start Guides to determine how each
device affects the PNG operation of the LMRC-213 and the
LMRC-213-347.
CONNECTIVITY
Ceiling Mount
DLM Local Network
Sensor
Low Voltage
LMRJ Cables
Dimmer
Daylight Sensor
0-10V Dimming control wires (available for each load)
MOUNTING THE CONTROLLER
Attaching LMRJ Cables
Remove rubber jack covers to use RJ45 receptacles.
Leave covers in place for all unused receptacles.
PLUG N' GO OPERATION (PNG)
Line
Earth Ground/Green wire
Voltage
Line/Hot
Black wire
Room
Controller
Neutral
White wire
Blue wire
to Load C
Deep J-Box
Yellow wire to Load B
Red wire to Load A
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Load A
Load B
ON/OFF/Dim
ON/OFF/Dim
2
Load
Examples
(any relay)
Switched
A
Switched
B
Ballast
Switched with
C
0-10 Volt control
Dimming Ballast
LED Driver, etc.
0-10V Connections
Gray (-)
Violet (+)
Load C
Blue LED
ON/OFF/Dim
ON when load is
ON.
Load button:
Press & release
for ON/OFF.
Press & hold to
Dim.