Component Layout Guidelines; General Wiring Guidelines - Eaton LVLD Serie Manual Del Usuario

Tabla de contenido

Publicidad

also recommended to follow the requirements of
ICEL 1004:2003.
In most cases, installation of a conversion kit will
invalidate the manufacturers guarantee and it is
the responsibility of the installer to comply with
the CE marking, Low Voltage and EMC directives.
If a previously installed light fitting is to be
converted, any components showing signs
of degradation should be replaced. It is also
recommended that all internal wiring should be
renewed using high temperature (105°C) PVC
cable or the type originally specified if it has a
higher rating.

COMPONENT LAYOUT GUIDELINES

The conversion kits are best installed inside the
light fitting, usually requiring the repositioning
of existing components (i.e. ballast and terminal
blocks). When installing inside the fitting:
Do not obstruct cable entries, mounting
facilities, lighting controllers or covers.
Do not locate the batteries or capacitor near
excessive heat sources, e.g. ballasts and
lamp ends.
The module should be placed as close as
possible to the ballast to keep wires short,
while being far enough away to prevent
overheating.
Ensure your layout doesn't interfere with
the essential safety features of the fitting
such as shrouding, earthing etc.
Avoid altering the fitting's normal lighting
distribution.
Space & temperature restrictions may require
remote mounting of the batteries or the complete
conversion kit in a special enclosure. If this
is necessary, it is not as important to take into
account the component temperatures but you
should note the following:
The cable to the fully remote enclosure
must not exceed 2m.
If mounted more than 1m from the light
fitting, the remote enclosure must be
connected using fire proof cable.
Battery leads must be as short as possible,
and the total resistance of the battery lead
must not exceed 0,05 ohms.
The indicating LED should be mounted
within the light fitting or remote enclosure
where it is clearly visible during normal
operation (mounting requires 0.25" or
6,35mm hole).

GENERAL WIRING GUIDELINES

Refer
to
the
connections and observe the following guidelines:
Always use high temperature 105°C PVC
cable (or a higher grade if originally used in
www.eaton.com
diagrams
for
typical
wiring
EN
7

Publicidad

Tabla de contenido
loading

Tabla de contenido