2.1 REMOTE ON/OFF
TTL High/PS-OFF; TTL Low/PS-ON
VIL=0.8Vmax, IIL=-1.6mAmax @Vin=0.4V
VIH=2.0Vmin @Iin=-200uA, VIH=5.25Vmax @open ckt.
2.2 HOLD-UP TIME
10msec (minimum) at 80% of full load at 230Vac input.
2.3 POWER GOOD DELAY
100-500 msec.
2.4 POWER FAIL DELAY
1 msec.
2.5 TURN-ON DELAY TIME
2000 msec max.At Nominal Line Full Load.
2.6 TRANSIENT OVERSHOOT
DC output transient step sizes as below table:
Output voltage
Max. step size
Load-changing repetition rate of 10m seconds.
At dynamic loading,regulation at the +5V,+3.3V,+12V outputs can go to -8%+5%
Load slew rated 1.0A/uS and capacitive load as below :
+5V
10000uF
2.7 RISE TIME
20ms max at full load.
3. PROTECTION:
When OVP ,OPP or short protection is triggered, the main outputs will be latched
off. The main outputs can be reset by cycling the DC remote on/off or AC power.
+5Vsb output is auto recovery when fault condition removed.
3.1 OVER VOLTAGE PROTECTION
+3.3V output
+5.0V output
+12.0V output 15.6 Vmax.
+5V
30%
+3.3V
10000uF
10000uF
4.5 Vmax.
7.0 Vmax.
+3.3V
30%
+12V
-12V
470uF
+12V
30%
+5Vsb
10000uF