ELX-2
Structural Rough-Ins
Mounting for standard ADA and TAS height shown.
Areas highlighted in gray require sufficient backing
compliant with local building codes.
11⁵⁄₈"
(295)
32"
(813)
31¼"
(793)
CODE
A
Install (1) ³⁄₈" wall anchor with a minimum pull-out force of 1,000 lb per local codes at locations shown
B
Install (2) wall anchors per bracket with a minimum pull-out force of 100 lb per local codes at locations shown
C
Rim Height
6
Wall Bracket
A
C
3¼"
(84)
Provide structural backing compliant with local building codes.
Vertical Height Adjustments
33½"
No Adjustment
30½"
Subtract 3"
26"
Subtract 7½"
3/2/2020
C
L
B
12¼"
(311)
19¾"
(502)
24"
(610)
Finished Floor
DESCRIPTION
Fixture Style
Standard ADA & TAS
Juvenile ADA & TAS
Bradley • 215-1807 Rev. F: ECN 19-08-037F
Secure bracket to wall using min.
(2) ³⁄₈" anchor bolts to the left of
C/L and min. (2) ³⁄₈" anchor bolts
to the right of C/L. The (2) anchor
bolts to the right of C/L must be
min. 16" apart from the anchor bolts
to the left of C/L. When mounting
is complete, check to ensure the
bracket is level.
A
C
B
32"
(813mm)
12¼"
26½"
(311)
(673mm)
19¾"
(502)
24"
(610)
Junior
Installation
(mm)
QTY.
2
4
2