EN
DE
FR
Tone
Tone Type
1.
970Hz (BS5839-1:2002)
2.
800Hz/970Hz @ 2Hz (BS5839-1:2002)
3.
800Hz – 970Hz @ 1Hz (BS5839-1:2002)
4.
970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)
5.
970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
6.
554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )
7.
500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000 Dutch Slow Whoop
8.
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
9.
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)
10.
550Hz/440Hz @ 0.5Hz
11.
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)
12.
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)
13.
1200Hz – 500Hz @ 1Hz (DIN 33 404)
14.
400Hz
15.
550Hz, 0.7s/1000Hz, 0.33s
16.
1500Hz – 2700Hz @ 3Hz (Vandal Alarm)
17.
Simulated Bell
18.
840Hz
19.
660Hz
20.
660Hz 1.8s ON/1.8s OFF
21.
660Hz 0.15s ON/0.15s OFF
22.
510Hz, 0.25s/ 610Hz, 0.25s
23.
800/1000Hz 0.5s each (1Hz)
24.
250Hz – 1200Hz @ 12Hz
25.
500Hz – 1200Hz @ 0.33Hz.
26.
2400Hz – 2900Hz @ 9Hz
27.
2400Hz – 2900Hz @ 3Hz
28.
800Hz – 970Hz @ 100Hz
29.
800Hz – 970Hz @ 9Hz
30.
800Hz – 970Hz @ 3Hz
31.
800Hz, 0.25s ON/1s OFF
32.
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
33.
340Hz
34.
1000Hz
35.
1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)
36.
660Hz 6.5s ON/13s OFF
37.
1000Hz/2000Hz, 1s each
38.
720Hz, 0.7s ON/0.3s OFF
39.
970Hz, 0.25s ON/OFF
40.
2800Hz, 1s ON/OFF
41.
2800Hz 0.25s ON/OFF
42.
2400/2900 @ 2Hz
43.
Chime, 554Hz/440Hz Single shot 'ding dong'
44.
Chime, 554Hz/440Hz Repeating 'ding dong'
45.
Chime, 970Hz/800Hz Single shot 'ding dong'
46.
Chime, 970Hz/800Hz Repeating 'ding dong'
47.
Hooter, Repeating
48.
Gentle alarm - Tone 2, rises slowly to full volume over 30s
49.
Time-Out Alarm – As Tone 2, cuts off after 10 mins
50.
Time-Out Alarm – As Tone 2, cuts off after 2 mins
51.
750Hz 0.33s ON/0.51s OFF
52.
750Hz 0.51s ON/0.33s OFF
53.
550Hz, 0.33s/1000Hz, 0.7s
54.
600Hz – 900Hz/ 0.9s
55.
660Hz – 680Hz/ 0.9s
56.
670Hz – 725Hz/ 0.9s
57.
920Hz – 750Hz/ 0.9s
58.
700Hz - 900Hz, 0.3s/0.6s OFF
59.
900Hz - 760Hz, 0.6s/0.3s OFF
60.
750Hz
61.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
62.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
63.
Power Only – Use with Stage 3 control for manual/intermittent horn triggering
EN54-3:2001+A1
Fire Alarm Device – Sounder
Type B: For indoor or outdoor use
PNS-0013/PNC-0013/15/21/48/50/29/34/52/53/54
Technical Data: Document 18-186529
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK
+44 1706 233879
NL
ES
PT
Tone Description / Application
+44 1706 223450
IT
SE
PL
Nexus 110 DC Sounder & Sounder-Beacon
Installation Instructions
Dip Switch
(S1/S2)
O-O-O-O-O-O
O-O-O-O-O-I
O-O-O-O-I-O
O- O- O -O-I- I
O-O-O-I-O-O
O-O-O - I-O -I
O-O-O-I- I- O
O - O - O - I - I - I
O-O-I-O-O-O
O-O- I- O-O- I
O- O-I- O- I-O
O - O - I - O - I - I
O-O-I- I-O- O
O - O - I - I - O - I
O - O - I - I - I - O
O - O - I - I - I - I
O-I-O-O-O-O
O- I- O- O-O-I
O-I- O- O-I- O
O - I - O - O - I - I
O- I-O -I- O-O
O - I - O - I - O - I
O - I - O - I - I - O
O - I - O - I - I - I
O-I- I- O-O- O
O - I - I - O - O - I
O - I - I - O - I - O
O - I - I - O - I - I
O - I - I - I - O - O
O - I - I - I - O - I
O - I - I - I - I - O
O - I - I - I - I - I
I-O-O-O-O-O
I-O- O- O-O- I
I- O-O-O-I- O
I - O - O - O - I - I
I- O-O-I- O-O
I - O - O - I - O - I
I - O - O - I - I - O
I - O - O - I - I - I
I- O-I- O-O-O
I - O - I - O - O - I
I - O - I - O - I - O
I - O - I - O - I - I
I- O - I - I - O - O
I - O - I - I - O - I
I - O - I - I - I - O
I - O - I - I - I - I
I- I- O-O- O-O
I - I - O - O - O - I
I - I - O - O - I - O
I - I - O - O - I - I
I - I - O - I - O - O
I - I - O - I - O - I
I - I - O - I - I - O
I - I - O - I - I - I
I - I - I - O - O - O
I - I - I - O - O - I
I - I - I - O - I - O
I - I - I - O - I - I
I - I - I - I - O - O
I - I - I - I - O - I
I - I - I - I - I - O
0832-CPD-0618 (Sounder-LED Beacon)
0832
0832-CPD-0619 (Sounder-Xenon Beacon)
07
0832-CPD-0620 (Sounder)
sales@klaxonsignals.com www.klaxonsignals.com
DK
3rd Stage
Peak Sound
Tone
Level
(dBA @1m, 24V DC) (mA Avg, 24V DC)
18
110
1
110
1
110
1
110
1
110
1
107
1
110
1
105
1
110
19
107
1
110
1
112
1
110
18
105
1
111
1
116
1
112
1
113
10
109
19
108
19
107
1
107
1
111
1
105
1
110
1
116
1
116
1
110
1
110
1
110
1
108
1
110
1
106
18
111
1
110
19
108
1
113
1
106
1
110
1
113
1
113
1
115
1
104
1
107
1
106
1
106
1
107
1
109
1
109
1
109
1
106
1
107
1
111
1
109
1
105
1
107
1
110
1
109
1
110
18
107
43
43
47
Issue 9.0 (May 2012) 18-186458-9
Copyright © Texecom Ltd
Sounder
Current
45
44
43
25
39
24
28
9
13
26
19
16
34
21
33
46
26
34
31
16
17
28
44
24
31
45
45
42
43
43
10
29
18
47
44
31
41
26
25
22
21
43
15
15
36
36
13
44
44
44
12
25
41
37
33
33
41
15
28
39