NOTES: DO NOT TAMPER WITH THE FLOAT SWITCH. THE NON RESPECT OF THE FOLLOWING POINTS
WILL AUTOMATICALY CAUSE THE CANCELLATION OF THE WARANTY OF THE PRODUCT
Before any operation on the float remember to disconnect the power supply from the main power.
Check that the maximum motor power does not exceed the float's electrical values.
in case of cable damage by the final user or installer, the float must be replaced.
Do not make any joint on the cable of the float switch, as immersion of such joints could cause short circuits or
electrical shocks.
USE:
Unlike normal floats, the level regulator is used in pairs of two of the same type to regulate water levels to a certain
height: one regulates the minimum level and the other regulates the maximum level. A third and fourth regulator can
also be used for minimum and maximum alarm respectively. To avoid damaging the cable, we recommend the Fixing
Kit (Fig.1)
The tank fills

TECHNICAL FEATURES:

AC: Max 10A (250V) resistive load - 8A (250V) motor load
Min 1200mW (12V/100mA)
B
REAKING CAPACITY
Operating temperature: min.-15°C – max.+50°C
Wire gauge: 8,8mm (0.35in)
Max depth: 20m
Protection Grade: IP68
Specific weight: 0,95 - 1,05 kg/dm³

TERMINAL CONNECTIONS:

The upstream circuit must protect the electric wires from the overcurrent. WARNING: lack of protection shall null
and void the warrany in the event the float breaks.
72.B1-XX00 (PVC) – 72.B1-XX01 (H07 RN-F): double function (the fitter can choose the emptying (Fig.2) or filling (Fig.3)
when installing):
Emptying: (Fig.2) when black and brown wires are used, the circuit opens when float is down and closes when the
float is up. Note: the blue/grey wire must be insulated.
Filling: (Fig.3) when black and blue/grey wires are used, the circuit closes when float is down and opens when the
float is up. Note: the brown wire must be insulated.
Fig.2 emptying
DC1: 6 A - 30 V DC
ENGLISH
High level starts the
pump
Low level stops the
The tank drains
Activation angle: 20°
Fig.3 filling
pump