MP-SENSOR
Start-up
Apply voltage
Segment
Type
check
Display
1.) Factory settings
Output 1
PSPDD / PSVDD
Hysteresis- Mode
4,6 bar / -0,46 bar
0,7 bar / -0,07 bar
NC-Mode
0 sec.
0 sec.
The Clear All special function loads the factory settings, and all
previous settings are cancelled.
2.)
Settings options
Output 1
Hysteresis
mode
Switching
threshold
Hysteresis
Normally
closed
Closing
delay
Release
delay
- The menu items listed under OU1 are settings specific to output 1
- The menu items listed under OU2 are settings specific to output 2
- The menu items listed under SF are general settings which
influence both outputs.
Output settings options
Hysteresis mode
- Switching threshold
- Hysteresis
- Type of contact (normally open, normally closed)
- Closing delay
- Release delay
Comparator mode
- upper switching threshold
- lower switching threshold
- Type of contact (normally open, normally closed)
- Closing delay
- Release delay
Special functions settings options
Pressure unit pico PSVDD => bar, mmHg, inHg, MPa
Pressure unit pico PSPDD => bar, psi, MPa
Clear All
=> factory setting loaded
Key lock activated = BLC, inactive = UnL
Rotate display 180°
3.)
General procedure for adjusting settings
By following the flow diagram, you can move to any menu item you wish
using the three buttons (Up, Down and Mode).
For example: output 2
-Comparator mode
-lower threshold
-upper threshold
-Position of normally closed contact
-Closing delay 0 sec.
-Release delay 0 sec.
Procedure: Measure mode output
a) Briefly press Mode button
b) Briefly press Up button
c) Briefly press Mode button to enter Menu level.
d) Proceed to desired menu item with Up or Down
button and confirm by pressing Mode button.
e) In this case: confirm HY2 with Mode button.
f) Go to the desired setting with the Up or Down button
In this case: CP2. Then confirm setting with Mode button.
g) To adjust further settings, follow the procedure in d) above.
In this case, set U-2 (lower threshold) and confirm
with Mode button.
h) Adjust the desired setting with the Up or Down button.
In this case: set U-2 to 0.50 and then confirm setting with Mode button.
i) Proceed in the same way for all other settings.
D-73765 Neuhausen
GB
Pressure
Measure mode
unit
display
Special
Output 2
functions
PSPDD / PSVDD
Pressure
Hysteresis- Mode
unit bar
7,9 bar / -0,79 bar
Unlock
0,7 bar / -0,07 bar
NC-Mode
0 sec.
0 sec.
Special
Output 2
funktions
Comparator
Pressure
mode
unit
Upper
Factory
switching
settings
threshold
Lower switch
Unlock
threshold
Normally
Rotate display
open
180°
Closing
delay
Release
delay
PSPDD = 3,0 bar
PSVDD = -0.3 bar
PSPDD = 5,0 bar
PSVDD = -0.5 bar
=> OU1 display
=> OU2 display
=> HY2 display
=> HY2 display flashes
=> U-2 display flashes
-
Tel. ++49 - (0)7158 / 98 784 90
pico PSPDD pressure / PSVDD vacuum
j)
To enter another setting level, e.g. output 1 (OU1) or special functions (SF),
you use the Up or Down button to go to the menu item rEt (Return). If this is
confirmed with the Mode button, you arrive at the previous level. In this case
you would arrive at the menu item OU2 and now you can switch between the
menu items Output 1 or Special functions with the Up or Down button in
order to adjust settings.
4.) Activate key lock
The locking function ensures that the switch settings are safeguarded against
unintentional changes or manipulation. To activate the locking function,
proceed as follows:
Starting state is Measure
Briefly press Mode button (select level)
Press Up or Down button until SF reached
Briefly press Mode button until menu entered
Press Up or Down button until UnL reached
Briefly press Mode button until menu entered
Set BLC with Up or Down button
Confirm setting with Mode button
5.) Deactivate key lock
Briefly press Up, Down and Mode buttons simultaneously
Briefly press Mode button once
Set UnL with Up or Down button
Confirm with Mode button
Return to Measure state via rEt (Return) menu item
6.) Selectable display units pico PSVDD-VACUUM *
The following units of measurement are available
Display
- Looking at the flow diagram, select the menu item SF
(special functions) and briefly press Mode button.
bar
- PU appears on the display (pressure unit).
KPa
- Select PU with Mode button. Now the desired unit can be
selected with the Up or Down button.
mmHg
- Confirm the selected unit with the Mode button and exit the
inHg
menu via the rEt function (Return).
* pico PSPDD – PRESSURE: bar, psi, MPa
7.)
Setting display to zero
Operate switch in Measure mode
Depress Mode button for 3 sec.
Display is set to zero
8.) Peak values
Briefly press Down button, the lowest measured value will be displayed for 3 sec.
Briefly press Up button, the highest measured value will be displayed for 3 sec.
9.) Error messages
Error messages
PSPDD / PSVDD
Overcurrent Out 1
Overcurrent Out 2
Vacuum instead of Pressure /
Vacuum instead of pressure /
pressure instead of vacuum
Pressure instead of Vacuum
Pressure / vacuum
Pressure / Vacuum applied
applied > pressure
range
EEPROM defective
Distance to zerro
higher than +/- 3% of t he
point > 3%
10.) Selecting the operating mode
Each output needs to be programmed individually, as they are completely independent
and can work in different operating modes and under various settings.
Hysteresis mode
10 bar
S
H
PSPDD
0 bar
0 bar
H
S
PSVDD
-1 bar
-
Fax ++49 - (0)7158 / 98 798 65
=> Display: Pressure activated
=> Display OU1
=> Display SF
=> Display PU
=> Display UnL
=> Display UnL flashes
=> Display BLC flashes
=> Display Measure
=> Display BLC
=> Display BLC flashes
=> Display UnL flashes
=> Display UnL static
Procedure for adjusting settings
Remedy
Cause
PSPDD / PSVDD
PSPDD / PSVDD
Output 1 overloaded
Increase load impedance
(current > 125 mA)
Output 2 overloaded
Increase load impedance
(current > 125 mA)
Apply pressure / vacuum
Set pressure / vacuum
exceeds pressure range
inside the pressure range
EEPROM defective, data
Switch defective, replace
memory defective
Vaccum or pressure was
Reset zero point to
ambient pressure
measuring range
Window Comparator mode
10 bar
U
b
0 bar
0 bar
b
U
-1 bar
-
www.mp-sensor.de
7