Silencing the alarm
Manually testing the system
Manually testing the auxiliary contact
System OK
Pump Running
AC Power Failure
Reverse Polarity
AC Power Failure
Highwater
Blown Fuse
Power OK Sys ON
Pump Failure
Battery Low
Battery Critical
Auto Test Fail
Sensor Failure
SILENCING & TESTING
To silence the alarm press the alarm silence/test button once and do not hold. This
will deactivate the alarm for a period of 24hrs.
Hold the Alarm Silence/Test button down for 10 seconds, the system will start a
diagnostic test and run the pump for 10 seconds
Hold the Alarm Silence/Test button down for 15 seconds, the unit will send a alarm
signal to the auxiliary contact. Note: This will activate any alarm/dialer that you have
DISPLAY MESSAGES
INFORMATIONAL MESSAGES
Displayed when no alarms are active and
the system is not running
Displays when the pump is on and the
system has been activated
Displayed when the system loses AC
power
ALARM MESSAGES
Battery RED/BLACK leads are reversed
Displayed when the system loses AC
power
System has failed or is not keeping up
with the incoming water
Pump fuse on controller has blown
AC Power is on but system is running
System is ok but pump isn't running
Battery voltage has dropped below 11.4V
Battery voltage has dropped below 10.2V
System did not pass auto test
Sensor is not getting a signal from the
controller
connected to the system.
System is working properly
System is working properly
If power in the house is on, check that the
unit is plugged in or the GFI/breaker has
Connect leads to correct terminals
If power in the house is on, check that the
unit is plugged in or the GFI/breaker has
not been tripped
Check display for additional message like
low battery or pump not running
Replace with another 20Amp fuse
Check your primary pump for failure
Check pump connections or inspect pump
Normal during extended loss of power
Replace battery if power remains out
Check display for additional messages
and/or call for service
Check the metal tip on the bottom of the
sensors for obstructions
5