In order that no hazardous CO2 concentrations emerge
when being used in a closed room, the following space
volumes may not be fallen short of:
Air exchange rate of 0.2/hour
24 3012 2065 TWISTFIRE NEW GENERATION S
• 108 m³ - this corresponds, e.g. at 2.5 m room
height, to an area of 5 x 9 m
24 3012 2070 TWISTFIRE NEW GENERATION L
• 216 m³ - this corresponds, e.g. at 2.5 m room
height, to an area of 9 x 9.6 m
The following table gives you a reference point for how you can bring about the appropriate air
exchange rate:
Air exchange per hour
Air exchange per hour
Explanation of the symbols used on the product
Position of the windows and doors
0 - 0.2
Windows, doors closed
0.3 - 3
Window tilted
2 - 10
Window half open
5 - 15
Window fully open
up to 40
Windows and doors opposite are open
Description
0.2
Air exchange rate due to leaks in the building
0.4 – 0.6
Typical air exchange rate for sealed buildings with
standard ventilation habits of the user
1
complete air exchange in the installation room within an hour
Do not fill with fuel when hot.
Air exchange rate of 0.5/hour
24 3012 2065 TWISTFIRE NEW GENERATION S
• 58 m³ - this corresponds, e.g. at 2.5 m room height,
to an area of 4 x 6 m
24 3012 2070 TWISTFIRE NEW GENERATION L
• 115 m³ - this corresponds, e.g. at 2.5 m room
height, to an area of 6 x 7.7 m
Do not fill with fuel during operation.