System Maintenance - Toshiba RBC-RD1-PE Manual Del Propietário

Detector de refrigerante
Ocultar thumbs Ver también para RBC-RD1-PE:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
All manuals and user guides at all-guides.com
K7127 Ref.Detect. O/M
6/3/01
System Maintainance
G
When cleaning the sensor plate, ensure that no cleaning agents are used, i.e. spray
cleaners and polishes.
G
Use a vacuum to clean the sensor ventilation slots, and then wipe with a dry soft
cloth.
G
Over long periods of time the sensor offset can slowly drift from zero. Therefore we
recommend that the sensor offset is verified on the detector on an annual basis to
retain accuracy and performance. The procedure for setting the zero offset is
described below:
o
Connect a DC volt meter across pins 1 and 3, refer to the diagram below. Also an
accessory is available which can be used to connect to the PCB.
Ext
Int
Reset
Reset
Pin 1
o
With the unit in a clean air (no contaminates, i.e. R407C) measure the DC voltage.
The offset voltage should be 0.25V DC, if the measured voltage is not the same
then the offset voltage must be adjusted.
8:36 am
Page 8
GB
A B C
JP
Pin 3
Sub PCB
8

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rbc-rd2-pe

Tabla de contenido