North American Certifications:

A.2
For Ex-i protection application
Connect the instrument to a proper intrinsically safe barrier.
Check the intrinsically safe parameters involving the barrier, equipment including the cable
and connections.
Associated apparatus ground bus shall be insulated from panels and mounting enclosures.
When using shielded cable, isolate the not grounded cable end.
Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the
Associated Apparatus.
Hart Communicator
For free access to the Hart bus in the explosive environment, ensure the instruments in the loop are
installed in accordance with intrinsically safe or non-incendive field wiring practices. Use only Ex
Hart communicator approved according to the type of protection Ex-i (IS) or Ex-n (NI).

FM Approvals (Factory Mutual)

Protections Methods:
Intrinsic Safety (FM 3009955)
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
IS Model Approved FY301- ab-cde/f
a = Digital indicator 0 (without indicator) or 1 (with digital indicator).
b = Mounting bracket 0 or 1.
c = Electrical connection 0 (1/2-14 NPT), A (M20) and B (PG13,5).
d = Type of actuator (not included) 1, 2, 3, 4, 5, 6, 7, 8 or Z.
e = Indication gage 0, 1, 2, 3, 4, 5 or Z.
f = Optional items H1 (316 SST Housing) or Blank
Explosion Proof (FM 3007267)
Class I, Division 1, Groups A, B, C and D
XP Model Approved FY301- ab-cde/f
a = Digital indicator 0 (without indicator) or 1 (with digital indicator).
b = Mounting bracket 0 or 1.
c = Electrical connection 0 (1/2-14 NPT).
d = Type of actuator (not included) 1, 2, 3, 4, 5, 6, 7, 8 or Z.
e = Indication gage 0, 1, 2, 3, 4, 5 or Z.
f = Optional items H1 (316 SST Housing) or Blank
Dust Ignition Proof (FM 3009955 and 3007267)
Class II, Division 1, Groups E, F and G
Class III, Division 1
Non Incendive (FM 3009955)
Class I, Division 2, Groups A, B, C and D
Environmental Protection (FM 3009955 and 3007267)
Options: Type 4X or Type 4
Special conditions for safe use:
Entity Parameters: Vmax = 30 Vdc Imax = 110 mA Ci = 8 nF Li = 12 uH
Temperature Class T4
Maximum Ambient Temperature: 60ºC
Drawings for manuals:
Label Plate: 102A-1207 and 102A-1330
Installation Drawing: 102A-0439