Ferroli DIVAcondens F24 Instrucciones De Uso, Instalación Y Mantenimiento página 31

Ocultar thumbs Ver también para DIVAcondens F24:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15
DIVAcondens F24/F28
Connection with separate pipes
C
5x
fig. 11 - Examples of connection with separate pipes (
Table. 4 - Typology
Type Description
C1X Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be
undergo similar wind conditions (within 50 cm)
C3X Roof vertical exhaust and intake. Inlet/outlet terminals like for C12
C5X Wall or roof exhaust and intake separate or in any case in areas with different pressures. The exhaust and
intake must not be positioned on opposite walls.
C6X Intake and exhaust with separately certified pipes (EN 1856/1)
B2X Intake from installation room and wall or roof exhaust
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
For connection of the separate ducts, fit the unit with the following starting accessory:
Ø 81
fig. 12 - Starting accessory for separate ducts
Before proceeding with installation make sure the maximum permissible length has not
been exceeded, by means of a simple calculation:
1.
Completely establish the layout of the system of split flues, including accessories
and outlet terminals.
2.
Consult the table 6 and identify the losses in meq (equivalent metres) of every com-
ponent, according to the installation position.
3.
Check that the sum total of losses is less than or equal to the maximum permissible
length in table 5.
Table. 5 - Baffles for separate ducts
Max. permissible length
Baffle to use
B
C
2x
1x
= Air /
Ø 81
041039X0
Cod. Kit 390C0110
Separate ducts
55 m
eq
0 ÷ 15 m
Ø 45
eq
15 ÷ 35 m
Ø 50
eq
35 ÷ 55 m
No baffle
eq
cod. 3541G922 - Rev. 01 - 04/2018
Table. 6 - Accessories
PIPE 1 m M/F
BEND 45° M/F
PIPE SECTION with test point
Ø 80
TERMINAL air, wall
FLUE Split air/fumes 80/80
= Fumes)
PIPE 1 m M/F
BEND 90° M/F
Ø 60
REDUCTION 80/60
TERMINAL fumes, wall with antiwind
Connection to collective flues
C
8X
fig. 13 - Examples of connection to flues (
Table. 7 - Typology
Type Description
C2X Intake and exhaust in common flue (intake and exhaust in same flue)
C4X Intake and exhaust in common and separate flues , but undergoing similar wind conditions
C8X Exhaust in single or common flue and wall intake
B3X Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in common
flue with natural draught
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
If the boiler is to be connected DIVAcondens F24/F28 to a collective flue or a single flue
with natural draught, the flue or chimney must be expressly designed by professionally
qualified technical personnel in conformity with the current regulations and be suitable
for sealed chamber units equipped with fan.
1KWMA83W
1KWMA65W
90° M/F
1KWMA01W
1KWMA70W
1KWMA85A
fumes, wall with antiwind
1KWMA86A
010027X0
Fume outlet only Ø80
010026X0 +
1KWMA86U
1KWMA89W
1KWMA88W
041050X0
1KWMA90A
ATTENTION: CONSIDER THE HIGH PRESSURE LOSSES OF Ø60 ACCESSORIES;
USE THEM ONLY IF NECESSARY AND AT THE LAST FUME EXHAUST SECTION.
C
2X
Losses in m
eq
Air
Fume exhaust
inlet
Vertical
Horizontal
1.0
1.6
2.0
1.2
1.8
1,5
2.0
0.3
0.3
2.0
-
-
5.0
-
12.0
-
4.0
6.0
4.5
5.0
7.0
C
4X
= Air /
= Fumes)
EN
31

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Divacondens f28

Tabla de contenido