en | Mounting
3

Mounting

Notice!
Smoke detectors are not to be used with detector guards unless the combination has been
evaluated and found suitable for that purpose.
Follow NFPA-72 guidelines for mounting locations. For commercial and industrial
installations, 30 ft. (9 m) spacing between smoke detectors is recommended.
The electrical boxes must be large enough to accommodate the number and size of
conductors as specified by the National Electrical Code or the local Authorities Having
Jurisdiction (AHJ).
3.1

Mounting the Detector

3
2
1
3
Figure 3.1: 6-inch and 4-inch Mounting Bases
Position
1
2
3
4
1.
Mount the base using the two oblong mounting holes (see Position 1).
If you mount the detector with a 6-inch base, first remove the base skirt (2) from the
mounting base using a screwdriver to release the 4 tabs (3).
2018.08 | 6.0 | F.01U.123.589
All manuals and user guides at all-guides.com
3
1
3
Description
Mounting holes
Base skirt
Release tabs
Semicircle notch
Installation Guide
Analog detectors and bases
4
1
Bosch Security Systems, Inc.
1