Installation Preparation
Questions? Call 844-GE4-PTAC (or 844-434-7822 ) or
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT –
•
instructions for local inspector's use.
IMPORTANT –
•
codes and ordinances.
Note to Installer –
•
instructions with the owner.
Note to Owner –
•
future reference.
• Proper installation is the responsibility of the
installer. Completed installation of the Zoneline
shall not be accessible to the general public.
• Product failure due to improper installation is not
covered under the Warranty.
• Team lift is recommended when moving unit.
• You MUST use all supplied parts and use proper
installation procedures as described in these
instructions when installing this air conditioner.
IMPORTANT ELECTRICAL
SAFETY—READ
CAREFULLY
WARNING
RISK OF ELECTRIC SHOCK.
• All electrical connections and wiring MUST be
installed by a qualified electrician.
• Follow the National Electrical Code (NEC) and/or
local codes and ordinances.
• For personal safety, this Zoneline unit and case
must be properly grounded.
• Protective devices (fuses or circuit breakers)
acceptable for Zoneline installations are specified on
the nameplate of each unit.
• Do not use an extension cord with this unit.
• Aluminum building wiring may present special
problems—consult a qualified electrician.
• When the unit is not running there is still voltage to
the electrical controls.
• Disconnect the power to the unit before servicing by:
1. Removing the branch circuit fuses or turning the
circuit breakers off at the panel.
2. Disconnecting the power cord from the unit.
14
Save these
Observe all governing
Be sure to leave these
Keep these instructions for
Visit our Website at:
ELECTRICAL
REQUIREMENTS
Wire Size
Use ONLY wire size recommended
for single outlet branch circuit
Fuse/Circuit
Use ONLY type and size fuse or
Breaker
HVACR circuit breaker indicted
on units rating plate. Proper over
current protection to the units is the
responsibility of the owner.
Grounding
Unit MUST be grounded from branch
circuit to unit, or through separate
ground wire provided on permanently
connected units. Be sure that branch
circuit is grounded.
Wire Sizing
Use recommended wire size given
in tables and install a single branch
circuit. All wiring must comply with
local and national codes.
NOTE: Use copper conductors
only.
NOTE: All field wiring must comply with NEC and
local codes. It is the responsibility of the installer
to ensure that the electrical codes are met.
• Use ONLY the wiring size recommended for single
outlet branch circuit.
• Proper current protection is the responsibility
of the owner.
Recommended Branch Circuit Wire Sizes*
Nameplate
Maximum Circuit
Breaker Size
15A
20A
30A
AWG - American Wire Gauge
* Single circuit breaker from main box
** Based on copper wire, single insulated conductor
at 600C
NOTE: Use copper conductors only.
WARNING
RISK OF ELECTRIC SHOCK.
Can cause injury or death. This appliance must be
properly grounded.
GEAppliances.com
AWG Wire Size**
14
12
10
49-5000640 Rev. 1