CONFIGURING THE PUMP PARAMETERS MANUALLY
The manual configuration wizard is a procedure in which the electric pump current and power factor (cosφ) must be entered
manually in a few steps.
• Open the menu
PUMP1 CONFIG
• See PARAMETER EDITING COMMANDS for how to edit the values of each individual parameter.
SELECT
PUMP1 CONFIG
9
PUMP1 CONFIG
WIZARD
PUMP1 CONFIG
CURRENT:5.0A
PUMP1 CONFIG
CURR TOUT:7s
54 | ENGLISH
• Close the electric pump delivery valve until the minimum current value is
I:6.2
displayed (I).
• Wait about 20 seconds to let the minimum current parameter (I) settle, and
then the procedure will go to the next screen.
• Press the
I:6.2
• Open the electric pump delivery valve until the maximum current value is
I:9.2A
displayed (I).
• Wait about 20 seconds to let the current parameter (I) settle, and then the
procedure will go to the next screen.
• Press the
I:9.2A
• Wait about 20 seconds to let the voltage parameter (V) settle, and then the
V:220V
procedure will go to the next screen.
• Press the
V:220V
• The procedure is complete, and the next screen will appear.
• Press the
SELECT
• Press the
• Do not consider this submenu. Go to the next one.
• Set the maximum permissible current of the electric pump (from the rating plate or
measured)
Default 5.0 A
• Set the overcurrent trip delay time.
Default 7 sec
key to save the CURR MIN parameter and go to the next screen.
key to save the CURRENT parameter and go to the next screen
key to save the VOLT MIN and VOLT MAX parameters.
key again to exit from the procedure
PUMP2 CONFIG
WIZARD
key to confirm the choice and enter the submenu
Range 0–18 A
Range 0–20 sec
Step 0.1
Step 1 sec