Saivod DHX-10D Manual Del Usuario página 76

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

result in the ignition of refrigerant in the atmosphere
from a leak.
4 CABLING
Check that cabling will not be subject to wear,
corrosion, excessive pressure, vibration, sharp edges
or any other adverse environmental effects.
The check shall also take into account the effects of
aging or continual vibration from sources such as
compressors or fans.
5 DETECTION OF FLAMMABLE REFRIGERANTS
Under no circumstances shall potential sources of
ignition be used in the searching for or detection of
refrigerant leaks. A halide torch (or any other detector
using a naked flame) shall not be used.
6 LEAK DETECTION METHODS
The following leak detection methods are deemed
acceptable
for
systems
containing
flammable
refrigerants. Electronic leak detectors shall be used
to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need recalibration.
(Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not
a potential source of ignition and is suitable for the
refrigerant used. Leak detection equipment shall be
set at a percentage of the LFL of the refrigerant and
shall be calibrated to the refrigerant employed and
the appropriate percentage of gas (25 % maximum)
is confirmed. Leak detection fluids are suitable for
use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine
may react with the refrigerant and corrode the
copper pipe-work. If a leak is suspected, all naked
flames shall be removed/extinguished. If a leakage
of refrigerant is found which requires brazing, all of
the refrigerant shall be recovered from the system, or
76

Publicidad

Tabla de contenido
loading

Productos relacionados para Saivod DHX-10D

Este manual también es adecuado para:

D002a-10l/m

Tabla de contenido