Auto Changeover Set Point Offset; (Dead Band) - GE RAK160W2 Manual Del Propietario & Instrucciones De Instalación

Termostato inalámbrico con velocidades de dos ventiladores
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Custom Settings
20 – AUTO CHANGEOVER SET POINT OFFSET

(DEAD BAND)

(00°F - 05°F; 01°F* default setting) Select the difference
between the guest-selected set point and the heat and
the cool set point when the thermostat is in the automatic
temperature control mode.
This value plus the 1st stage differential defined in
settings 02 and 04, defines the temperature at which the
thermostat would automatically change heating/cooling
modes.
This feature allows adjusting the dead band between the
heat and the cool set points in automatic changeover
mode in order to avoid the system from bouncing back
and forth between heating and cooling under normal
operating conditions.
25