Pressure Check; Leak Check; Electrical Connection - Furrion FGH12D2-BL Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

line are sealed at time of installation.
2. Check the pipe fittings for leaks using a soapy water
solution. See "Leak Check" section.(Fig.6)
Fig. 6

Pressure Check

1.
Turn LP gas off to the appliance.
2. Remove the Screw with the sealing gasket from the
pressure test port on the range.(Fig.7)
Fig. 7
3. Using the rubber tube from the pressure check
measuring device, slide the rubber tube down over the
gas pressure test port. The rubber tube should seal
around the pressure test port on the range.(Fig.8)
4. Turn on the LP gas to the appliance.
5. The pressure gauge tester should measure between 11"-
13.8" WC.
Fig. 8
6. Turn off the LP gas to the appliance.
7.
Remove the rubber tube of the pressure check
measuring device.
8. Replace the screw with the gasket from step 2. Before
replacing the screw, inspect the rubber gasket seal for
any signs of damage. Replace seal if damaged.
9. Tighten the screw to 1.3 Nm to 1.7 Nm.
NOTE: Ensure the product is gas leak checked after the
pressure check test is completed by also testing the pressure
check port screw. If any leaks are detected around the
pressure check port screw and gasket, a new one can be
purchased. Call Furrion support for a replacement.

Leak Check

Gas leaks may occur in your system and result in
a dangerous situation. Always perform a leak test
for possible leaks according to the manufacturer's
instructions after installation and before any operation.
Gas leaks may not be detected by smell alone. Gas
suppliers recommend you purchase and install a UL
approved gas detector.
FIRE OR EXPLOSION
Extinguish all open flames.
Never leak test when smoking. Never use a flame.
Do not use the appliance until the connection has been
leak-tested and does not leak.
1.
Ensure all control knobs are in the OFF position.
2. Apply a gas leak detection liquid (soapy water) to the
connections. If there are bubbles presented, there is a
gas leak.
3. If a gas leak is detected, tighten the loose joint, or replace
the faulty part with a replacement part recommended by
Furrion authorized retailer.

Electrical Connection

PRODUCT DAMAGE HAZARD
Connect to 12V DC service only.
Connect only to protected circuit fused for not more
than 15 Amps.
DO NOT hi-pot range unless electronic ignition system
has been disconnected.
Connection wires are located at the right back of the unit.
Connect to the red wire to the positive DC supply wire
from the distribution box and connect to the black wire the
negative DC supply wire.(Fig.9)
Fig. 9
NOTE: Ensure to connect the wires with the correct polarity.
Red is "+" and Black is "-".
+
-
22#AWG
VDD
GND
Pulse igniter
- 6 -
WARNING
WARNING
CAUTION
22#AWG
Knob light switch
Blue
Red
Lamp board(Front)
Lamp board(Back)
CCD-0006069 Rev: 07-09-22
Blue
Red

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

2022115111

Tabla de contenido