Technical Data - Refco Gobi II Guía De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Gobi II:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Instruction manual Gobi II
DO NOT use tools to connect the tubing.
DO NOT operate this product in ambient temperatures below
5 °C (41 °F).
DO NOT operate with incoming water above a temperature of
40 °C (104 °F).
CAUTION: Do not allow any chemicals to come in contact with
this condensate pump. Please remove the pump and water sensor
before using any coil cleaning solutions and other chemicals. Flush
the evaporator coils with water before reinstalling the condensate
pump and water sensor.

Technical data

Maximum flow rate:
Maximum suction:
Maximum head:
Maximum horizontal run:
Sound:
Voltage:
Power:
Alarm relay:
Weight:
Discharge star tube:
Packaging dimensions:
Bulk pack dimensions:
Color:
Protection:
Operation temp:
Compliance:
Capacity
0
1
2
20
18
16
14
12
10
8
6
4
2
0
0
2
4
6
8
42 l/Hr. (11 GPH)
3 m (9.80 ft.) self priming
20 m (65.60 ft.)
100 m (330 ft.) at 0 head and 0 suction
19dBA at 1 m DIN EN ISO 3741:2011 / DIN EN ISO 3744:2010
100 ~ 240 VAC 50/60 Hz auto sensing universal power input
8 W during maximum operation at 110 V
7 Amps contacts with integrated replaceable 6.3A fuse 5 × 20 mm
1'100 g (2.45 lb.)
6.25 mm I.D. (1/4") × 1 m (3.3 ft.)
250 x 340 x 54 mm (9.9 x 13.4 x 2.1 inches)
10 Pcs dimensions are 590 x 265 x 365 mm (23.2 x 10.4 x 14.4 inches)
RAL #9003 white
Fully potted, IP-44
Ambient 5°C to 40°C (41°F to 104°F) / Water 5°C to 40°C (41°F to 104°F)
Capacity US G/Hr
3
4
5
10
12
14
16
18
20 22
Capacity l/Hr
Ensure the evaporator coils are free of chemicals before reinstalla-
tion of the REFCO Gobi II pump.
CAUTION: This appliance incorporates an earth connection for
functional purposes only.
6
7
8
24 26 28 30 32 34 36 38 40 42 44
Gobi II & Combi at full power
9
10
60
50
40
30
20
10
0
English
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

3004145

Tabla de contenido