Basic Configuration - Danfoss AK-RC 204B Guia De Instalacion

Ocultar thumbs Ver también para AK-RC 204B:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Basic configuration

Level 1
Level 2
Description
b00
Delay of all functions on receiving power supply
b01
Cold room light timing
Function of password
b10
0=Inactive, 1=Block access to parameters, 2=Block keypad
PAS
Access code (Password)
bcn
b20
MODBUS address
Communication speed:
b21
0=9600 bps, 1=19200 bps, 2=38400 bps, 3=57600 bps
b22
Acoustic alarm enabled: 0= No, 1=Yes
Work units: 0=°C, 1=°F
Unt
EP
Exit to level 1
Inputs and outputs
Level 1
Level 2
Description
Connected probes
I00
1=Probe 1 (Cold room), 2=Probe 1 (Cold room) + Probe 2 (Evaporator)
Configuration of digital input 1
0= Deactivated, 1=Door contact, 2=External alarm,
I10
1)
3=Severe external alarm, 4=Change of SP, 5=Remote defrost,
6=Defrost block, 7= Low pressure switch, 8=Remote Stand-by
Polarity of the digital input 1
I11
0=Activates on closing contact; 1=Activates on opening contact
Configuration of digital input 2
0= Deactivated, 1=Door contact, 2=External alarm,
3=Severe external alarm, 4=Change of SP, 5=Remote defrost,
I20
6=Defrost block, 7=Register probe, 8=Probe 2° evaporator
In0
9=High pressure switch for Hot Gas, 10=Remote Stand-by
Polarity of the digital input 2
I21
0=Activates on closing contact; 1=Activates on opening contact
Configuration of relay AUX1
0=Deactivated, 1=Compressor/Resistor sump, 2=Light, 3=Virtual control,
o00
1)
4=Alarm
Configuration of relay AUX2
0=Deactivated, 1=Alarm, 2=Light, 3=Virtual control,
o10
4=Door frame resistance, 5=Defrost 2° evaporator,
6=Same as solenoid status, 7=Same as unit status
EP
Exit to level 1
* According to wizard.
It can only be modified using the configuration wizard (InI).
1)
Not available in AK-RC 204B
2)
Available in AK-RC 204B only
3)
HACCP alarm
Level 1
Level 2
Description
h1
Maximum temperature of HACCP alarm
HCP
h2
Maximum permitted time for activation of the HACCP alarm (0=Disabled)
EP
Exit to level 1
6 | AN41473467835501-000102
3)
2)
Values
Min.
Min.
bps
Values
,
2)
Values
°C/°F
H.
© Danfoss | Climate Solutions | 2022.08
Min.
Def.
Max.
0
0
255
0
0
999
0
0
2
0
0
99
0
0
247
0
2
3
0
1
1
0
1
1
Min.
Def.
Max.
1
2
2
0
*
8
0
*
1
0
0
10
0
0
1
0
*
4
0
2
7
Min.
Def.
Max.
-50
99
99
0
0
255

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ak-rc 205c

Tabla de contenido